        NT935BH 

 

  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

FAN TEST 

 

It is possible, by programming (

HFn

), to make sure that the fans are operated for 5 minutes every 

xxx

” hours, regardless 

of the temperature values  of the columns  or the  environment  (e.g.:  with  HFn  =  001  the  fans  are  activated  for  5  minutes 
every hour). 
This function is designed to periodically check the operation of the fans and of their control equipment. 
Setting 

NO

, this function is inhibited. 

 

To enable the HFN function, read the programming section on pages 13-14. 

  
 

               IMPORTANT INFORMATION

 

  

Before carrying out the isolation test of the electrical panel the control unit is installed on, disconnect it together 
with the sensors from the power supply to prevent it from being seriously damaged.

 

  
 

OUTPUT RS485 MODBUS 

INTRODUCTION TO THE MODBUS INSIDE MODULE 

  

The MODBUS INSIDE expansion module is incorporated within the monitoring unit and allows data transfer on a RS485 
line with MODBUS RTU protocol, maximum 32 devices. 

 

OPERATING NOTES 

 

 

For  correct  functioning  of  the  module  it  is  necessary  to  set  the  RS485  network  set-up  parameters:  address,  baud  rate, 
parity bit.See programming steps 36 to 41 on page 11. 
The serial communication of the temperature control monitoring unit is only active when the NT935BH-D is in temperature 
control mode in one of the intended modes (Scan, Auto, Man and T.Max). 
When  other  functions  such  as  programming,  programming  display  and  relay  test  are  activated,  the  ModBus 
communication is temporarily deactivated. 

 

  

DATA TRANSMISSION ON MODBUS NETWORK 

  

The  MODBUS  INSIDE  internal  module  makes  it  possible  to  connect  the  NT935BH-D  control  unit  to  an  RS485  network 
with Modbus RTU protocol in order to be able to read the data indicated in the Modbus table, page 21, and to be able to 
write the data indicated in the paragraph notes for remote programming.  The module is always in slave mode. 
The NT935 RS485 control unit is in communication with the network only when it is in temperature reading mode, while it 
is inactive when in the following modes: display, programming and test relays. 
  

RS485 ELECTRICAL CONNECTIONS 

  

As far as the signal cable to be used in order to ensure the correct network operation is concerned, we recommend you 
follow the provisions of the EIA RS485 standard which suggests using a 24AWG twisted pair.

 

The twisted pair that connects units in RS485 might need a 120 ohm end resistor on the last unit of the series. 
Connect the twisted pair paying attention to polarities and lay the network avoiding to make sharp bends or ring windings 
in order not to modify line impedance. If necessary, the GND terminal for grounding is also available. 
Always position the RS485 twisted pair far from power cables. 

 

  

  
  
  
  
  
 
 
DATA FRAME 

 

  

 
The frame in asynchronous transmission consists of: 1 start bit, 8 data bits, 1 parity bit (even or odd, if the parity has been 
set) and 1 stop bit.  
With NO parity (none) it is possible to select N-1 (1 stop bit) or N-2 (2 stop bit).   
The permitted baud rates are: 2400, 4800, 9600, 19200 and 38400. 
If not otherwise specified, the word length (DATA) is 16 bits. 

  
 

1MN0095 REV. 0 

Содержание NT935BH-D

Страница 1: ...s with ISO9001 certified quality system http www tecsystem it R 1 0 10 06 20 Translations of the original instructions ENGLISH TECSYSTEM S r l 20094 Corsico MI Tel 39 024581861 Fax 39 0248600783 NT935...

Страница 2: ...NG NOTES 15 TEMPERATURE SENSORS MEASUREMENT SIGNAL TRANSFER TEMPERATURE SENSOR DIAGNOSTICS 16 VOTING FUNCTION PROGRAMMED DATA DIAGNOSTICS TEMPERATURE DIAGNOSTICS COOLING FAN CONTROL 17 FANS DIAGNOSTIC...

Страница 3: ...TA FRAME 19 DATA PACKET FUNCTION CODE CODE 3 10 CODE 16 10 NOTES FOR REMOTE PROGRAMMING ERROR CODES 20 UNACCEPTABLE DATA ILLEGAL DATA POLLING FREQUENCY MODBUS MAPPING TABLE 21 9 FAILSAFE FUNCTION 26 1...

Страница 4: ...e control unit disconnect it immediately and contact technical service CLEANING Disconnect the power cable before cleaning the control unit use a dry cloth to dust it without any solvent or detergents...

Страница 5: ...ing torque 0 5Nm 1 Terminal 12 poles pitch 3 81 sensors Pt100 Code 2PL0420 Screw tightening torque 0 25Nm 1 Terminal 4 pitch poles 3 81 for BLDC output Code 2PL0368 Screws tightening torque 0 25Nm 1 T...

Страница 6: ...ation management relay SPST FAN 2 Output relays with 10A 250Vac res COS 1 contacts TRBH output FAN1 control bars B1 B2 RS485 output Modbus RTU DIMENSIONS 100x100 mm din43700 prof 131mm including termi...

Страница 7: ...te of FAN1 and FAN2 Temperature control from 0 C to 240 C 2 alarm thresholds for channels 1 2 3 2 alarm channels for channel 4 1 activation threshold FAN1 ON TRBH 2 ON OFF thresholds FAN 2 ventilation...

Страница 8: ...ication 5 FAULT red LED 16 3 digit channel display 6 FAN 1 TRBH signalling yellow 17 T max mode selection red LED 7 FAN 2 yellow LED 18 Man mode selection yellow LED 8 Display mode selection key 19 Au...

Страница 9: ...epairs 4 Pt Err This message appears when it is detected that one or more PT100 sensors are not working correctly FOC FCC and FCD indications in the temperature sensor diagnostics paragraph on page 16...

Страница 10: ...ks 1 Control unit 2 Panel hole dimensions 0 8 mm tolerance 3 Identification label 1 Control unit 3 Locking screws 2 Fixing blocks 4 Cross head screwdriver 1X100mm ASSEMBLY 1 1MN0007 REV 0 2 3 1 2 3 4...

Страница 11: ...sensors white red red 4 Relay FAN2 2 Power supply 85 260Vac cc 50 60Hz 5 FAN1 BLDC output Control Box connection 3 Relays ALARM TRIP FAULT 6 RS485 output Modbus RTU Pt100 CONNECTION EXAMPLE Note imag...

Страница 12: ...one of the methods described below does not monitor heat also the relay will all be banned The fault contact switches and the fault LED flashes Vis Programming display PRG programming Relay test The...

Страница 13: ...H4 is enabled with NO the CH4 is disabled 10 The ALARM threshold for CH4 is displayed the Alarm led flashes If CH4 NO jump to step 16 Default NO 11 Set the desired threshold Default 120 C 12 The TRIP...

Страница 14: ...FE info on page 26 31 Select YES or NO Default NO 32 FLS TRIP is displayed Blinking TRIP LED 33 Select YES or NO Default NO 34 FLS FAULT is displayed Blinking FAULT LED 35 Select YES or NO Default YES...

Страница 15: ...rcuit couples capacitively with the conductors in particular with unscreened cables The effect of this coupling creates a signal that overlaps the signal transmitted by the nearby conductors causing i...

Страница 16: ...se alarms generated by installation errors By activating the VOTING YES function the control unit compares the temperature values recorded on the monitored CH1 CH2 CH3 channels and enables the switchi...

Страница 17: ...1 C at 230 C range 0 C to 240 C or 1 C 190 C range 40 C to 200 C NOTE fan speed regulation rpm with selections different from B1 3 and B2 3 is managed with reference HOT channel the hottest channel of...

Страница 18: ...unication is temporarily deactivated DATA TRANSMISSION ON MODBUS NETWORK The MODBUS INSIDE internal module makes it possible to connect the NT935BH D control unit to an RS485 network with Modbus RTU p...

Страница 19: ...ng 00000000 xxxxxxx0 x n d Also in the remote programming phase via ModBus it must be considered that the Alarm thresholds must be lower than the Trip thresholds and that the Fan on thresholds must be...

Страница 20: ...Status Value FCD max see table SYSTEM Setting and Status Value Voting max see table SYSTEM Setting and Status Note If the value of Voting is higher than the max value expected for the model in questi...

Страница 21: ...channels 2 ASCII R 6 Options see note Options see note R 7 00 Wrong datum received R see tab 8 00 Info various causes R see tab 9 00 Controls W see tab SYSTEM Setting and Status Address LO 10 Data HI...

Страница 22: ...s 1 4 Address LO 10 Data HI Data LO Notes 1 Notes 2 R read W write RW read write 25 2 compl sign 2 compl Ch1 temper 10 C 240 C 48 C 200 C R 26 2 compl sign 2 compl Ch1 max temperat 0 C 240 C 0 C 200 C...

Страница 23: ...C 240 C 1 C 200 C AL RW 40 2 compl sign 2 compl Ch4 temper trip set point 1 C 240 C 1 C 200 C TRP RW 41 00 00 R 42 00 00 R 43 00 00 R 44 00 00 R 45 00 TRBH _1 speed M1 M6 motors R 46 00 TRBH _1 motors...

Страница 24: ...0 Ch4 Setting See Notes CHx RW 61 00 00 R 62 00 00 R 63 00 00 R 64 00 00 R CHANNELS 1 4 Status Address LO 10 Data HI Data LO Notes 1 Notes 2 R read W write RW read write 65 Ch1 story Ch1 status See No...

Страница 25: ...n STORY BIT 7 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 TRIP ALARM FOC FCC RELAY STATUS coil energising status BIT 7 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 Relay FAULT 1 ON TRIP Relay 1 ON ALARM Re...

Страница 26: ...tches closed when a fault condition is identified see paragraph on alarms and ventilation on page 12 Setting NO NO Fail safe the contact 11 12 is positioned as normally closed switches open when a fau...

Страница 27: ...al transfer on page 15 Identification of a sensor fault or faulty connection In case of a faulty connection or sensor fault a quick positive or negative variation in temperature might occur leading to...

Страница 28: ...eck the connections and the terminal board The temperature shown by one or more channels is wrong Contact the TECSYSTEM Technical Department Sudden trip of the main switch The temperature is on standa...

Страница 29: ...pean directive 2012 19 EU on electrical and electronic waste WEEE Any electrical or electronic equipment marked with this symbol must be disposed of separately from normal domestic waste Returning of...

Отзывы: