23
T154 WS
SETTINGS SCREEN
In the settings screen it is possible to modify the programming of the T154 WS control unit.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
As for the panel programming also for programming through WEB SERVER it is necessary to follow these rules:
AL. = ALARM
≥
TRIP
FAN = FAN-OFF
≥
FAN-ON. (FAN1)
The cells of the editable values are accessible in white, the grey cells are not accessible. The programming limits of the
monitored parameters are shown in the table above.
SAVE SETTINGS key
After entering the
PIN CODE
, default 00000, by pressing the
SAVE SETTINGS
key the user updates the programming data
of the T154 WS device. The control unit will lose the connection for a few seconds, the device will start after which the new
values will be available on the updated screen.
Incorrect programming of the device will result in the display of an error POP UP window with the relative signalling; the data
update will not be processed.
(*) Note: PIN CODE settings and operation on page 28
16
17
Key:
BACK
Return to the
HOME
screen
1
Channel reference and enabling
CH1-CH2-CH3 and CH4
10
Enabling of FAILSAFE FUNCTION
Relay: ALARM-TRIP-FAULT
2
Enabling FAN 1 channel
CH1-CH2-CH3
11
FAN 1 limit programming boxes
On and Off (from 1°C to 240°C)
3
Enabling FAN 2 channel CH4
(Not available for the T154 WS model)
12
FAN 2 limit programming boxes
(Not available for the T154 WS model)
4
INTELLIFAN FUNCTION enabling
(Not available for the T154 WS model)
13
NETWORK SETTINGS key
5
ALARM limit programming box
(from 0°C to 239°C)
14
E-MAIL SETTING key
(Not available for the T154 WS model)
6
TRIP limit programming box
(from 1°C to 240°C)
15
OPTIONS button
7
HFN setting box (from 0h to 200 h)
0= function disabled
16
SAVE SETTINGS key
8
FCD setting box (from 0°C to 30°C)
0= function disabled
17
PIN CODE box (*)
9
Voting setting box: (0-NO) (1-YES)