TROUBLESHOOTING
CAUSES AND SOLUTIONS
The control unit does not switch on and the supply
to terminals 40-42 is correct.
Check that: the connector is firmly inserted in its place, the connection
wires are tight and that there are no obvious signs of burns on the
connectors. Turn off the power supply and carry out the above
instructions, restore the voltage.
CH4 is in FAULT for FOC
(only the 3 Pt100 sensors are connected)
Programming error of the CH4 / YES control unit.
Check and repeat the
programming on page 13-14 select CH4 /NO.
One of the three/four channels is in FAULT for
FOC/FCC
Check the connections of the Pt100 probes, check the indications
provided in the paragraphs:
transport of measurement signals and
thermometric probe diagnostics on page 16.
When turned on, the indication "ECH" appears
A strong disturbance has damaged the memory data. See the
paragraph for programmed data diagnostics on page 17.
All the Pt100 sensors are in FCC.
Incorrect sensor connection, the terminal block has been inserted
upside down.
Check the connections and the terminal board.
The temperature shown by one or more channels
is wrong.
Contact the
TECSYSTEM
Technical Department.
Sudden trip of the main switch. The temperature
is on standard levels. Just one channel has
caused the trip.
Check the temperatures recorded in T-MAX, check the indications
provided in the paragraphs:
transport of measurement signals and
thermometric probe diagnostics on page 16. Activate the FCD function.
FCD warning
See the FCD function on page 19.
During operation of the web server it is not
possible to display the date and time and also the
graphics screen does not work.
In the
Access point
mode select settings/Options and enter the date
and time in the
Set data/time (AP mode)
box
In
Station
mode, select settings/Networking and enter time.google.com
in the
Server NTP
box
The web server has been set in Access Point
mode but the network cannot be identified.
With the control unit off, keep the access point button pressed, then
power the device and release the button after approximately 5 seconds.
The TECSYSTEM network (S/N + YEAR) will appear and connect to
the network using the TECSYSTEM password. Open your browser and
type in the address 192.168.8.8 use the web server bar to enter the
Settings page, press the Network setting button and check: the
ACCESS POINT selection, the settings SSID and Password, press
save.
The web server has been set in Station mode
but the web server cannot be accessed.
With the aid of a device with a Wi-Fi connection (PC, Smartphone or
Tablet) with the control unit off, keep the access point button pressed,
then power the device, and release the key after approximately 5
seconds. Launch the search for the Wi-Fi network from your device.
The TECSYSTEM network will appear (S/N + YEAR), connect to the
network using the TECSYSTEM password. Open your browser and
type in the address 192.168.8.8, use the web server bar to enter the
Settings, page, press the Network setting button and check: the
STATION selection, the settings: IP
– GATEWAY -SUBNET MASK –
NET WORK SSID
– PASSWORD,
press save.
Contact the TECSYSTEM Technical Department if the problem persists.