T154 WS
PITCH
PRESS
EFFECT
PRESS
NOTES
1
Press and hold the PRG button until the display shows
SET PRG
2
Select PRG SET to proceed with programming or PRG 1
to load the default values
PRG 1 default data
3
The ALARM threshold for (CH 1-2-3) is displayed.
Set the desired threshold, the Alarm LED flashes
Default 90°C
4
The TRIP threshold for (CH 1-2-3) appears and the Trip
LED flashes.
5
Set the desired threshold
Default 119°C
6
The display shows FAN1 (CH 1-2-3)
Fan1 LED flashes.
Default YES
7
Select YES/NO
8
The display shows (CH4)
Enabling CH4
9
Select YES or NO
with YES the CH4 is
enabled
with NO the CH4 is
disabled
10
The ALARM threshold for (CH4) appears and the Alarm
LED flashes.
If CH4=NO jump to step
16, Default NO
11
Set the desired threshold
Default 120°C
12
The TRIP threshold for (CH4) appears and
the Trip LED flashes
13
Set the desired threshold
Default 140°C
14
The display shows FAN1 for CH4
15
Select YES/NO
Default NO
16
The display shows ON,
FAN1 LED flashes
FAN1 NO jump to step 20
17
Set the desired threshold FAN1 ON
Default 70°C
18
The display shows OFF,
FAN1 LED flashes
19
Set the desired threshold FAN1 OFF
Default 60°C
PROGRAMMING
T154 WS