8
2.6 User (Control) Terminals (For Standard H & C type)
200V: 1 ~ 2 HP, 400V: 1 ~ 3HP
200V: 3 ~ 40 HP, 400V: 5 ~ 75HP, 575V:1~10HP, 690V: 15~75HP
R1A R1B R1C
R2A
R2C
RJ45
200V: 50 ~ 150 HP, 400V: 100 ~ 425HP, 690V: 100~270HP
R2A R2C R1A R1B R1C
RJ45
Description of User
Terminals
Type
Terminal
Terminal Function
Signal Level / Information
Digital
input
signal
S1
2-wire forward/ stop (default)
*1
Signal Level 24 VDC
(photo isolated)
Maximum current: 8mA
Maximum voltage: 30 Vdc
Input impedance: 4.22k
Ω
S2
2-wire reversal/ stop (default)
*1
S3
Multi-speed/ position setting command 1 (default)
*1
S4
Multi-speed/ position setting command 2 (default)
*1
S5
Multi-speed/ position setting command 3 (default)
*1
S6
Fault reset (default)
*1
S7
JOG frequency command (default)
*1
S8
External B.B.(Base Block) stop (coast to stop)
(default)
*1
24V
Power
supply
24V
Digital signal SOURCE point (SW3 switched to
SOURCE )
±15%,
Max. output current: 250mA
(The sum of all loads
connected )
24VG
Common terminal of Digital signals
Common point of digital signal SINK ( SW3 switched
to SINK )
Analog
input
signal
+10V
Power for external speed potentiometer
+10V (Max. current , 20mA)
-10V
Only above 200V 3HP/ 400V 5HP (include) support
this terminal function
-10V (Max. current , 20mA)
AI1
Multi-function analog input for speed reference (0-
10V input)/(-10V~10V input)
From 0 to +10V,
From -10V to +10V
Input impedance : 20K
Ω
Resolution: 11bit + 1
AI2
Multi-function analog input terminals
*2
, can use SW2
to switch voltage or current input (0~10V)/(4-20mA)
From 0 to +10V,
From -10V to +10V
Input impedance: 200K
Ω
From 4 to 20 mA
Input impedance: 250K
Ω
Resolution: 11bit + 1
GND
Analog signal ground terminal
----
E
Shielding wire’s connecting terminal (Ground)
----
Analog
output
AO1
Multi-function analog output terminals
*2
(0~10V
output)
From 0 to 10V,
From 4 to 20mA
Содержание A510s
Страница 1: ......
Страница 60: ...2 1 4 1 5 11 55 07 00 5 5 15Hp 15 1 6 25 14 104 140 F 10 40 60 C 95 RH...
Страница 61: ...3 2 2 1 NFB AC NFB NFB NFB 200mA 0 1 V TYPE AC AC EMC R S T E...
Страница 103: ...A 3 Type 1 During installation all conduit hole plugs shall be removed and all conduit holes shall be used 690V 80A...
Страница 111: ......