Group 08: Protection Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
Frequency (01-
02)
08-59
Fire Mode
Motor
Direction
0: Forward
1: Reverse
0 Note4
08-60
Fire Mode
Password
00000~65534 0
Note4
Note: Models of 200V 50HP and 400V 100HP and
above don’t have this function.
Group 09: Communication Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
09-00
INV
Communicati
on Station
Address
1~31 1
*3
09-01
Communicati
on Mode
Selection
0: MODBUS
0
*3
09-02
Baud Rate
Setting (bps)
0: 1200
4 *3
1: 2400
2: 4800
3: 9600
4: 19200
5: 38400
09-03
Stop Bit
Selection
0: 1 Stop Bit
0 *3
1: 2 Stop Bit
09-04
Parity
Selection
0: No Parity
0 *3
1: Even Bit
2: Odd Bit
09-05
Communicati
on Data Bit
Selection
0: 8 Bit Data
0 *3
1: 7 Bit Data
09-06
Communicati
on Error
Detection
Time
0.0~25.5 0.0
*3
09-07
Fault Stop
Selection
0: Deceleration to
Stop Based on
Deceleration Time 1
when
Communication
Fault Occurs.
3 *3
1: Coast to Stop
when
Communication
Fault Occurs.
2: Deceleration to
Stop Based on
Deceleration Time 2
when
Communication
Fault Occurs.
3: Keep Operating
when
Communication
Fault Occurs.
09-08 Comm. Fault 1~20
1
*3
Group 09: Communication Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
Tolerance
Count
09-09 Waiting Time 5~65
5
*3
09-10
Reserved
09-11 Bluetooth
0: Disable
1: Enable
09-12
Bluetooth
Password
0~65534
*3: Parameter 09 does not be influenced by 13-08
(Restore Factory Setting)
Group 10: PID Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
10-00
PID Target
Value Source
Setting
1: AI1 given
1
2: AI2 given
3: PI given
4:10-02 given
5: Reserved
6: Frequency
Command (00-
05)
10-01
PID Feedback
Value Source
Setting
1: AI1 given
2
2: AI2 given
3: PI given
10-02
PID Target
Value
0.00~100.00 0.00
*1
10-03
PID Control
Mode
xxx0b: PID
Disable
0000b
xxx1b: PID
Enable
xx0xb: PID
Positive
Characteristic
xx1xb: PID
Negative
Characteristic
x0xxb: PID Error
Value of D
Control
x1xxb: PID
Feedback Value
of D Ctrl
0xxxb: PID
Output
1xxxb: PID
Frequency
Command
10-04
Feedback
Gain
0.01~10.00 1.00
*1
10-05
Proportional
Gain (P)
0.00~10.00 1.00
*1
10-06
Integral Time
(I)
0.00~100.00 1.00
*1