Group 07: Start /Stop Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
07-27
Start Selection
after Fault
during SLV
Mode
0: Start with
speed search
0
1: Normal start
07-28
Start after
External Base
Block
0: Start with
speed
search
0
1: Normal start
07-29
Run
Command
Selection at
the Action of
DC Braking
0: Not Allowable
to Run
0
1: Allowable to
Run
07-30
Low Voltage
Level
Selection
0: Disable
0
1: Enable
07-31
**Low Voltage
Run
Frequency
0.00~599.00 10.00
07-32
Speed
Search Mode
Selection
0: Disable
0
1: Mode1:
Execute a
Speed Search at
Power On
2: Execute a
Speed Search
each time
07-33
Start
Frequency of
Speed
Search
Selection
0: Maximum
Output
Frequency of
Motor
0
1: Frequency
Command
07-34
Start short-
circuit braking
time
0.00~100.00 0.00 Note1
07-35
Stop Short-
circuit braking
time
0.00~100.00 0.50 Note1
07-36
Short-circuit
braking
current limited
0.0~200.0 100.0 Note1
07-37
~
07-41
Reserved
07-42
Voltage Limit
Gain
0.0~50.0 0
Note2
07-43
Short-circuit
Braking Time
of PM Speed
Search
0.00~100.00 0.00 Note3
07-44
DC Braking
Time of PM
Speed
Search
0.00~100.00 0.00 Note3
07-45
STP2
Function
Selection
0: STP2 Enable
0 Note4
1: STP2 Disable
07-46 DC Injection 0~150
100 Note5
Group 07: Start /Stop Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
Current Limit
07-47
PM Speed
Switching
Frequency
Mode
0: Disabled
0 Note8
1: Mode 1
2: Mode 2
*07-13 Low Voltage Detection Level, it is enable when
07-30 Low Voltage Level Selection set 0 (Enable) and
lower frequency limit set to 250V.This application is
for Emergency power supply (EPS)
* *If the maximum output frequency of motor is over
300HZ, the frequency resolution is changed to 0.1Hz
Group 08: Protection Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
08-00
Stall
Prevention
Function
xxx0b: Stall
prevention is
enabled in
acceleration.
0000b
xxx1b: Stall
prevention is
disabled in
acceleration.
xx0xb: Stall
prevention is
enabled in
deceleration.
xx1xb: Stall
prevention is
disabled in
deceleration.
x0xxb: Stall
prevention is
enabled in
operation
x1xxb: Stall
prevention is
disabled in
operation
0xxxb: Stall
prevention in
operation is based
on deceleration
time of speed-
stage 1.
1xxxb: Stall
prevention in
operation is based
on deceleration
time of speed-
stage 2.
08-01
Stall
Prevention
Level in
Acceleration
20~200
HD:150
ND:120
08-02
Stall
Prevention
Level in
Deceleration
200V: 330V~410V
385V
400V: 660V~820V
770V
575V:900~1000
950V
690V:1080~1200