30
Group 08: Protection Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
Time in
Operation
08-23
Ground Fault
(GF)
Selection
0: Disable
0
1: Enable
08-24
External Fault
Operation
Selection
0: Deceleration
to Stop
0
1: Coast to Stop
2: Continuous
Operation
08-25
Detection
Selection of
External Fault
0: Immediately
Detect when the
Power is
Supplied.
0
1: Start to Detect
when the
Operation is
Started.
08-26
~
08-29
Reserved
08-30
Run
Permissive
Function
Selection
0: Deceleration
to Stop
0
1: Coast to Stop
08-31
~
08-34
Reserved
08-35
Motor
Overheating
Fault
Selection
0: Disable
0
1: Deceleration
to Stop
2: Coast
to Stop
3: Continue
Running
08-36
PTC Input
Filter Time
Constant
0.00 ~ 5.00
2.00
08-37
Fan Control
Function
0: Start in
operation
0
1: Permanent
Start
2: Start in high
temperature
(Note)
08-38
Delay Time of
Fan Off
0~600 60
08-39
Delay Time of
Motor
Overheat
Protection
1~300 60
08-40
Motor2
Acceleration
Stall
Prevention
Level
20~200
HD:150
ND:120
08-41
Motor2
Acceleration
Stall
1~100 50
Group 08: Protection Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
Prevention
Limit
08-42
PTC
Protection
Level
0.1~10.0V 0.7
08-43
PTC Restart
Level
0.1~10.0V 0.3
08-44
PTC Warning
Level
0.1~10.0V 0.5
08-45
Reserved
08-46
Temperature
Agree Level
0~254°C 0
Note4
08-47
Temperature
Reset Level
0~254°C 0
Note4
08-48
Selection of
Fire Mode
0: Disable
1: Enable
0 Note4
08-49
Multi-Function
Input
Terminal
Status of Fire
Mode
0
:
Reset after
Power Off
1
:
Reset after
Terminal
Removed
0 Note4
08-50
Multi-Function
Terminal
Status of Fire
Mode
XXX0b: S6 A
contact
XXX1b: S6 B
contact
0000b Note4
08-51
Motor Speed
Setting
Source of Fire
Mode
0
:
Fire Mode
Speed (08-52)
1
:
PID Control
2
:
AI2
0 Note4
08-52
Motor Speed
of Fire Mode
0.00~100.00 100.00 Note4
08-53
PID Detection
Level of Fire
Mode
0~100 0
Note4
08-54
Delay Time of
Fire Mode
PID Loss
0.0~10.0 1.0
Note4
08-55
PID
Feedback
Loss
Detection
Selection of
Fire Mode
0
:
Keep
Running
1
:
Fire Mode
Speed (08-52)
2
:
Maximum
Output
Frequency (01-
02)
1 Note4
08-56
Detection
Level of Fire
Mode AI2
Signal
0.0~100.0 80.0 Note4
08-57
Delay Time of
Fire Mode AI2
Signal Loss
0.0~10.0 1.0
Note4
08-58
Selection of
Fire Mode AI2
Signal Loss
0
:
Keep
Running
1: Fire Mode
Speed (08-52)
2: Maximum
Output
1 Note4
Содержание A510s
Страница 1: ......
Страница 60: ...2 1 4 1 5 11 55 07 00 5 5 15Hp 15 1 6 25 14 104 140 F 10 40 60 C 95 RH...
Страница 61: ...3 2 2 1 NFB AC NFB NFB NFB 200mA 0 1 V TYPE AC AC EMC R S T E...
Страница 103: ...A 3 Type 1 During installation all conduit hole plugs shall be removed and all conduit holes shall be used 690V 80A...
Страница 111: ......