ENGLISH
UPS EVO DSP MM RM
11
User’s manual
5.1.4 Acoustic Alarm
Description
Buzzer Status
OFF
UPS status
Bypass Mode
Beeping once every 2 minutes
YES
Battery Mode
Beeping once every 4 seconds
Fault Mode
Beeping continuously
Warning
Overload
Beeping twice every second
NO
Low Battery
Beeping once every second
Battery Unconnected
Over Charge
EPO condition
Fan failure/Over Temperature
Charger failure
Input Circuit failure
Overload (3 times in 30 min)
Fault
Vdc Bus Start failure
Beeping continuously
YES
Vdc Bus Over
Vdc Bus under
Vdc Bus Unbalance
Vdc Bus short-circuit
Inverter Soft Start failure
High Inverter Voltage
Low Inverter Voltage
Inverter Output short-circuit
Power Fault
Battery SCR short-circuit
Inverter short-circuit
Battery Voltage Loss
Parallel Communication failure
Output short-circuit
Over Temperature
CPU Communication failure
Overload
Note:
OFF = YES
means that the buzzer can be muted or stopped
OFF = NO
means that the buzzer can NOT be muted or stopped
Содержание EVO DSP MM 10.0
Страница 2: ......
Страница 32: ...ENGLISH User s manual 28 UPS EVO DSP MM RM...
Страница 60: ...ITALIANO Manuale utente 56 UPS EVO DSP MM RM...
Страница 61: ......
Страница 62: ......
Страница 64: ...TECNOWARE s r l www tecnoware com...