ENGLISH
UPS EVO DSP MM RM
21
User’s manual
FAULT EVENT
FAULT CODE
ICON
FAULT EVENT
FAULT CODE
ICON
Vdc Bus Start failure
01
None
Power fault
1A
None
Vdc Bus Over
02
None
Battery SCR short-circuit
21
None
Vdc Bus under
03
None
Inverter short-circuit
24
None
Vdc Bus Unbalance
04
None
Battery Voltage Loss
28
Vdc Bus short-circuit
05
None
Parallel Communication failure
35
None
Inverter Soft Start failure
11
None
Output short-circuit
36
None
High Inverter Voltage
12
None
Over Temperature
41
None
Low Inverter Voltage
13
None
CPU Communication failure
42
None
Inverter Output short-circuit
14
Overload
43
Fault Table
9
Communication Interfaces
The UPS is factory-equipped with
RS232 and USB Communication Interfaces
. On the UPS rear side there are the
connections of the Interfaces.
Only one of the RS232/USB communications can be activated at one time. To activate RS232 communication it is
sufficient to connect the RS232 cable only; to activate USB communication it is sufficient to connect the USB cable
only.
The RS-232 and USB signals are all isolated through photo-couplers from the dangerous voltages that are
present inside the UPS.
It is possible to use a
SNMP (Single Network Management Protocol) Interface
to connect the UPS to a LAN (Local
Area Network). The SNMP interface is optional.
We advise you to follow the steps below explained to install the interface correctly:
1.
Remove the metallic panel (#6, figure 4) that covers the slot for SNMP interface.
2.
Put the SNMP Interface into the slot and fix it with screws.
3.
Connect the LAN cable to SNMP interface and follow the included instruction to make the interface working
well.