In order for this procedure, you must have a minimum of 5 lbs (2.3kg) of liquid refrigerant in
the storage tank.
1.Connect the hoses as shown
2. Turn the MODE valve to the Recover position.
3. Open the Vapor and Liquid valve of the storage tank.
4. Power on, and start the compressor.
5. Open the INPUT valve and OUTPUT valve of the machine.
6. Throttle the OUTPUT valve of the machine so that the output pressure is 100psi greater
than the input pressure, but never more than 300psi.
7. Run until tank is cold.
TANK COOLING PROCEDURE (OPTIONAL)
Set up your equipment as shown, it is possible to cool the storage tank during the recovery procedure if necessary.
1. Open the vapor valve of the storage tank (it is closed while recovering).
2. Close the two valves of the manifold gauge set.
3. Follow the sixth and seventh items of the tank Cooling Procedure.
ALTERNATIVE COOLING PROCEDURE (OPTIONAL)
Manifold gauge set
Input
Input
HVAC
System
Vapor
Liquid
Output
Output
Vapor
Vapor
Scale
Scale
Liquid
Liquid
16