1. Make sure this recovery machine is in good operating condition.
2. Make sure all connections are correct and tight .
3. Open the liquid port of the storage tank.
4. Make sure the MODE valve is set on RECOVER.
5. Open the output port of the recovery machine.
6. Open the liquid port on your manifold gauge set; opening the liquid port will remove the liquid from the
system first. After the liquid has bee n removed, open the manifold vapor port to finish evacuating the system.
SPECIFICHE
Refrigerants
R-12, R22, R-134a, R-401A, R401B, R401C, R402A, R402B,
R404A, R406A, R407B, R407C, R407D, R408A, R409A, R410A,
R411A, R411B, R-412A, R500, R502, R507, R509
Voltage
110/120 VAC 60 Hz 220-240 VAC 50 Hz
Compressor
1/2HP Oil-less
Max current
4 A a 50 Hz 9 A a 60 Hz
HP Shut-off 38bar/550psi
38 bar/550 pps
Recovery Rate
Vapor 0,25 kg /min.
Liquid 1,80 kg/min.
Push-Pull 6,25 kg/min.
LP Shut-off
15” Hg
80% Capacity Shut-off
Optional
Operating Temp.
0-40°C
Case
Blow Molded High Impact Polyethylene
Dimensions
19.1 Lx8.7 Wx14.4 H (485mm x220 mm x365mm)
Net Weight
33lbs (15kg)
STANDARD LIQUID/VAPOR RECOVERY
PROCEDURE
13