9
2 - SYSTEM RESOURCES
The TFA2-596 and TFA4-1192
fi
re detection panels are designed and manufactured in accordance with the standards
EN 54-2:1997 + A1:2006 (control panel) and EN 54-4:1997 + A1:2002 + A2:2006 (power supply).
It was designed under a quality system certi
fi
ed ISO 9001 that involves the application of a set of rules for the design and all
subsequent activities necessary for the production. All the components of the equipment were selected for the intended purposes.
Their speci
fi
cations are guarenteed, if the environmental conditions outside the casing correspond to those speci
fi
ed for the class
3K5 of the standard EN 60721-3-3:1995.
The control panels should be installed in indoor areas, monitoring of temperature and humidity is not required.
The control panels consist of a metal casing with space for two 12V/7.2Ah batteries, a CPU board, which integrates the user
interface consisting of a display and a keypad, a switching 24V/2.7Ah power supply (ALSW2827) and a terminal board.
The TFA2-596 control panel manages 2 and the TFA4-1192 manages 4 detection loops.
The number of available detection loops can be increased by connecting other control panels.
The maximum network con
fi
guration includes 16 control panels with 4 detection loops.
General speci
fi
cations
TFA2-596
TFA4-1192
Max. network con
fi
guration (16 control panels)
Repeaters
16
16
Max. 256 (16 x 16)
Detection loop
2
4
Max. 64 (4 x 16)
Detectors per loop
199
199
Total detectors
398 (199 x 2)
796 (199 x 4)
Max. 12736 (796 x 16)
Modules per loop
99
99
Total modules
198 (99 x 2)
396 (99 x 4)
Max. 6336 (396 x 16)
Zones
300
300
Max. 4800 (300 x 16)
Virtual zones
100
100
Max. 1600 (100 x 16)
Access periods
32
32
Max. 512 (32 x 16)
Access levels
4
4
4
Codes
10
10
10
Formulas
200
400
400
Alarm plans
100
200
200
N.B.
Although the control panel with 4 loops is able to manage a total of 1,192 detection devices (det call points), the standard EN 54-2 chapter 13.6 provides
that a failure may not affect more than 512 detectors and/or manual call points and their designated functions. Therefore, the maximum number of connectable
detectors/call points to each control panel is 512, multiplied by 16 control panels equals 8,192.
Warning:
the TFA2-596 and TFA4-1192 control panels are certi
fi
ed with the following options with requirements from EN 54-2
7.8
Outputs to
fi
re alarm devices
7.11
Output delays
7.12
Dependencies on more than one alarm signal (type B)
8.3
Failure signals from points
9.5
Disablement of addressable points
10
Test conditions
Warning:
the power supply of the TFA2-596 and TFA4-1192 control panels are certi
fi
ed to the requirements of EN 54-4
5.1
Power supply from the main power source
5.2
Power supply from the stand-by power source (battery)
5.3
Battery charging and check
5.4
Recognition and signaling of power supply failures
Содержание Tecnofire TFA2-596
Страница 2: ...TFA2 596 TFA4 1192 2...
Страница 4: ...TFA2 596 TFA4 1192 4...
Страница 10: ...TFA2 596 TFA4 1192 10...
Страница 14: ...TFA2 596 TFA4 1192 14...
Страница 28: ...TFA2 596 TFA4 1192 28...
Страница 32: ...TFA2 596 TFA4 1192 32...
Страница 40: ...TFA2 596 TFA4 1192 40...
Страница 50: ...TFA2 596 TFA4 1192 50...
Страница 62: ...TFA2 596 TFA4 1192 62 NOTES...
Страница 63: ......