TFA2-596 - TFA4-1192
57
TFA4-1192
TFPS-5 - No. 2
TFPS-5 - No. 1
TFA4-1192
TFPS-5 - No. 1
TFPS-5 - No. 3
TFPS-5 - No. 2
10-6 - TFA4-1192 additional power supply connection
Connection of one or two additional power supplies
The outputs OUT A, OUT B and OUT C of each TFPS-5 power supply must be connected in parallel and must then be connected
one to the terminals 29 and 30 and the other to the terminals 31 and 32 of the control panel.
Connection of two or more additional power supplies
The outputs of each TFPS-5 power supply must be connected in parallel. The positive and negative voltages of the
fi
rst power
supply must be connected to the terminals 29 and 30 of the control panel. The negative voltages of the other power supplies must
be connected in common, their positive voltages must be uncoupled with a Schottky diode SB1240 (12A-40V) and downstream
must be connected in common. The resulting pair of wires must be connected to the terminals 31 and 32 of the control panel.
TOTAL CURRENT PROVIDED
TFA4-1192
12Ah
TFPS-5 - No. 1
17Ah
TFPS-5 - No. 2
17Ah
Total
46Ah
TOTAL CURRENT PROVIDED
TFA4-1192
12Ah
TFPS-5 - No. 1
17Ah
TFPS-5 - No. 2
17Ah
TFPS-5 - No. 3
17Ah
Total
63Ah
Содержание Tecnofire TFA2-596
Страница 2: ...TFA2 596 TFA4 1192 2...
Страница 4: ...TFA2 596 TFA4 1192 4...
Страница 10: ...TFA2 596 TFA4 1192 10...
Страница 14: ...TFA2 596 TFA4 1192 14...
Страница 28: ...TFA2 596 TFA4 1192 28...
Страница 32: ...TFA2 596 TFA4 1192 32...
Страница 40: ...TFA2 596 TFA4 1192 40...
Страница 50: ...TFA2 596 TFA4 1192 50...
Страница 62: ...TFA2 596 TFA4 1192 62 NOTES...
Страница 63: ......