Tecnoalarm Tecnofire TFA2-596 Скачать руководство пользователя страница 50

TFA2-596 - TFA4-1192

50

Содержание Tecnofire TFA2-596

Страница 1: ...Installation Release 3 2 FW release 2 0 00 Models TFA2 596 TFA4 1192 Programming SW release 5 4 Update 07 2019 Language English TFA2 596 TFA4 1192 Addressable re alarm systems...

Страница 2: ...TFA2 596 TFA4 1192 2...

Страница 3: ...according to the following standards Control panels EN 54 2 1997 A1 2006 TFA2 596 Certification number 0051 CPR 0389 TFA4 1192 Certification number 0051 CPR 0388 Power supply EN 54 4 1997 A1 2002 A2 2...

Страница 4: ...TFA2 596 TFA4 1192 4...

Страница 5: ...ety 17 4 5 Secondary power supply 18 5 USER INTERFACE 5 1 Control panel 19 5 2 Access levels and codes 19 5 3 Function keys 20 5 4 Signaling LED 21 5 5 Viewing of operating states 22 5 6 Notification...

Страница 6: ...supply 49 10 CONNECTION 10 1 Detection loop connection 51 10 2 Siren connection 52 10 3 RS485 bus connection 53 10 4 Potentiation of the secondary power supply 56 10 5 TFA2 596 additional power supply...

Страница 7: ...e of the products acquired through specific training at Tecnofire division of Tecnoalarm S r l Environmental requirements The control panel and all the system components must be installed inside struc...

Страница 8: ...econdary battery power supply of the control panel and of the auxiliary power supplies Checking the operational state of the batteries and self powered devices sirens and telephone transmitters Checki...

Страница 9: ...192 Max network configuration 16 control panels Repeaters 16 16 Max 256 16 x 16 Detection loop 2 4 Max 64 4 x 16 Detectors per loop 199 199 Total detectors 398 199 x 2 796 199 x 4 Max 12736 796 x 16 M...

Страница 10: ...TFA2 596 TFA4 1192 10...

Страница 11: ...nage encrypted transmissions using customized passphrases Control panel network The network can be composed of a total of 16 addressable control panels connected through the RS485 serial bus The netwo...

Страница 12: ...r and the measures to be taken to deal with the alarm in the specific zone Programmable outputs In addition to the mandatory alarm failure and reset outputs the control panel features 2 programmable o...

Страница 13: ...200 TFA2 596 Alarm plans 200 TFA4 1192 100 TFA2 596 Access periods 32 Calendar Quadrennial programmable Test call with TCP IP Expandability Serial expansions max 16 TFT 7 TFT 7S Telephone communicator...

Страница 14: ...TFA2 596 TFA4 1192 14...

Страница 15: ...FOR INSTALLATION CPU board 12V 12Ah batteries Speaker Terminal board NTC probe for battery temperature monitoring USB port ALSW285PFC power supply Mounting holes TTL port Ground connectors Cable entr...

Страница 16: ...mong these standards we mention non exhaustive list EN 50200 EN 60228 EN 50363 EN 60332 EN 50267 IEC 60332 IEC 61034 IEC 6754 The installer shall ascertain the current legislative requirements for his...

Страница 17: ...d Mains connection 230V AC The mains cable is not included To reduce the risk of electric shocks in normal operating conditions observe the following precautions Use a double insulated cable with shie...

Страница 18: ...re of the battery via the NTC Negative Temperature Coefficient probe and adjusts the charging voltage of the batteries according to the themperature measured The NTC probe must be connected to the ded...

Страница 19: ...the RESET key B Switch the operating state of the control panel monitored not monitored C Manually activate an evacuation alarm D Access the list of menus reserved to level 2 E Stop and reset the sir...

Страница 20: ...lit The display alarm notifications remain visible MONITORED Toggle of the Monitored system mode N B This function only works if the option has been programmed 1 Press MONITORED 2 Enter level 2 code T...

Страница 21: ...f Sirens not stopped On Sirens stopped exclusion Yellow Exclusion of system devices Off No device excluded On At least one device excluded Siren fail EXCL Yellow Failure or exclusion of the sirens Off...

Страница 22: ...edgment of an event causes the muting of the speaker and the automatic display of the contents of the storage folder of the acknowledged event At the bottom the display shows 6 folders in which the ev...

Страница 23: ...02 2019 08 00 00 08 00 00 08 00 00 Access level 1 Access level 1 Access level 1 Level 2 Level 3 Level 4 Test 0000 Alarm 0001 Preal 0000 Tech Al 0000 Failure 0000 Excl 0000 08 03 2018 08 00 00 Alarm 2...

Страница 24: ...OK LED on MONITORED LED on or off depending on the selected state TX CARRIED OUT LED off All the other LED are off No siren is active No output is active 16 02 2019 08 00 00 Access level 1 Level 2 Lev...

Страница 25: ...d The display shows the technical prealarm state Signaling after the first acknowledgment The speaker is muted The TECHNICAL ALARM LED turns on steadily The display shows the list of active technical...

Страница 26: ...e control panel and the devices connected on the loop has broken down Active fire alarm This icon signals that the indicated device is in alarm state Detectors maintenance request This icon signals th...

Страница 27: ...e is over In this case to stop the notification it is necessary to reset the control panel 16 02 2019 08 00 00 Access level 1 Failure Failure Control panel 1 Aurora Hotel Console 1 Communication missi...

Страница 28: ...TFA2 596 TFA4 1192 28...

Страница 29: ...isabled the return to normal operating conditions does not automatically acknowledge all notifications It is necessary to reset the control panel 5 Switch on with battery power only Control panel swit...

Страница 30: ...st frequency 30 minutes Delay of failure notification 2 hours Signaling on occurence of failure The BATTERY LED starts flashing Signaling on notification of failure The control panel display shows BAT...

Страница 31: ...ns on steadily The GENERAL FAILURE LED starts flashing The failure relay is activated Reset of faillure notifications The failure notifications are reset after detecting for 60 seconds that the power...

Страница 32: ...TFA2 596 TFA4 1192 32...

Страница 33: ...ces with other zones 5 It must include minimum 1 device 6 It can include a total of 32 devices limitation valid only for fire zones DEFAULT ZONE FEATURES 1 It is a non programmable single knock fire z...

Страница 34: ...ector of the zone switches to alarm The timeout can be set by steps of 5 minutes from 0 infinite to 60 minutes N B The Behavior after prealarm setting can have an effect on the alarm release Prealarm...

Страница 35: ...BEHAVIOR AFTER PREALARM The zone is in stand by state A device in prealarm state switches the zone to prealarm Double knock zone prealarm timeout Behavior after prealarm On the basis of the setting t...

Страница 36: ...echnical alarm of the zone and trigger the output specifically programmed for technical alarm If a device generates a prealarm the zone will switch to prealarm state No alarm No alarm No alarm No alar...

Страница 37: ...tate continues Zone switches to alarm None Alarm No alarm Flag Behavior after prealarm No alarm TECHNICAL ZONE BEHAVIOR AFTER PREALARM The zone is in stand by state A device in prealarm state switches...

Страница 38: ...ates the alarm delay If the prealarm is not acknowledged by the operator within the alarm delay the prealarm is automatically converted into an alarm If the prealarm is acknowledged by the operator th...

Страница 39: ...2 39 A Alarm No alarm MONITORED SYSTEM MODE ALARM TRIGGERING FROM A MANUAL CALL POINT The zone is in stand by state An alarm from a manual call point in alarm state pressed immediately triggers the al...

Страница 40: ...TFA2 596 TFA4 1192 40...

Страница 41: ...l 22 alarm relay otput ALL terminals 1 2 3 and the relay output RESET terminals 16 17 are not supervised type C E J according to EN 54 1 nomenclature Therefore in accordance with EN 54 2 they may not...

Страница 42: ...itive input for power supply Siren output Notes Max current Positive power supply voltage for siren Controlled siren output reversed polarity in alarm 750mA 24V DC Negative power supply voltage for si...

Страница 43: ...No SIR output failure No Monitored control panel No KEY jumper inserted No Prog enabled No Status battery No Control panel reset No Status battery failure No Technical prealarm Yes Ethernet conector R...

Страница 44: ...9 OUT2 terminals 10 11 12 OUT3 terminals 13 14 15 OUT4 terminal 20 OUT5 terminal 21 OUT6 terminal 22 alarm relay otput ALL terminals 1 2 3 and the relay output RESET terminals 16 17 are not supervised...

Страница 45: ...ly Negative input for power supply Positive input for power supply Siren output Notes Max current Positive power supply voltage for siren Controlled siren output reversed polarity in alarm 750mA 24V D...

Страница 46: ...evice including outputs No Alarm from device under test No Exclusion of control panel outputs No System failure No At least one zone under test No Evacuation No Control panel under maintenance No Low...

Страница 47: ...ways be open In some procedures such as firmware upgrade the jumper must temporarily be closed JP3 CLR The jumper is used to clear programming and restore the default settings In normal operating cond...

Страница 48: ...The USB port allows to connect the control panel directly to a PC for programming of the control panel and upgrade of its firmware This connection supports only the standard Tecnofire protocol from t...

Страница 49: ...c N B The voltage value measured at the battery charger output is subject to variations due to the temperature of the battery The battery temperature is measured by a probe mounted on the battery surf...

Страница 50: ...TFA2 596 TFA4 1192 50...

Страница 51: ...EXCL IP PSTN FAIL EXCL ZONE IN TEST SYSTEM MONITORED MAINS PWR OK NETWORKED DEVICES TX CARRIED OUT EVACUATE RESET ACK MONITORED STOP RESET SIR ESC BACK Control panel working Level 2 Version 2 0 00 ENG...

Страница 52: ...between terminals 25 and 26 If one siren is connected a 47K resistor must be connected in parallel next to the siren If multiple sirens are connected a 47K resistor must be connected in parallel next...

Страница 53: ...reating a network of maximum 16 control panels The master and slave bus can be connected in open or closed loop mode In this latter case the loop wired to the Master Bus port is closed on the Slave Bu...

Страница 54: ...nnection to Master control panel Repeater Bus continues SW1 1 OFF Repeater Bus continues SW1 1 OFF Repeater Bus continues SW1 1 OFF Repeater Bus continues SW1 1 OFF Master control panel Bus terminatio...

Страница 55: ...ON 2 3 4 1 ON 2 3 4 1 ON 2 3 4 1 ON 2 3 4 1 ON 2 3 4 1 ON 2 3 4 1 ON 2 3 4 1 ON 2 3 4 1 Connection of repeaters in open loop to Master control panel with fiber optic converter Repeater Bus continues...

Страница 56: ...ol panel is equipped with dedicated terminals for the connection of one or more power supplies TFPS 5 compliant to EN 54 4 The operation of the TFPS 5 connected on the loop is supervised by the system...

Страница 57: ...outputs of each TFPS 5 power supply must be connected in parallel The positive and negative voltages of the first power supply must be connected to the terminals 29 and 30 of the control panel The ne...

Страница 58: ...act PTC protected I max 0 75A Normally closed contact Normally open contact N B The state indicated for the terminals 8 and 9 is in the condition of unpowered telephone communicator With the telephone...

Страница 59: ...form the firmware upgrade of the telephone communicator In normal operating conditions the jumper must always be open During firmware upgrade via serial port the jumper must temporarily be closed Supe...

Страница 60: ...B The address 0 disables the external Ethernet interface Accepted addresses range from 1 to 16 All other addresses are reserved END OF SERIAL BUS Insert on the last device of the serial bus SPECIAL P...

Страница 61: ...st device 2 Unused reserved 3 BOOT function ON Programming mode BOOT function enabled OFF Normal operating mode 4 CLR function ON Programming mode CLR function enabled OFF Normal operating mode Termin...

Страница 62: ...TFA2 596 TFA4 1192 62 NOTES...

Страница 63: ......

Страница 64: ...ri 38 10099 San Mauro T se Torino Italy Manufacturing plant Strada del Cascinotto 139 54 10156 Torino Italy Tel 39 011 22 35 410 Fax 39 011 27 35 590 info tecno redetection com www tecno redetection c...