8-2 - Fire zones
Single-knock
fi
re zone
The alarm of a single device (single-knock) is suf
fi
cient to generate the alarm of the zone and initiate the alarm procedure
programmed for the zone and the evacuation siren. If a device generates a prealarm, the zone will switch to prealarm state.
Double-knock
fi
re zone
The prealarm or alarm of a single device generates a prealarm in the zone, the intervention of a second device causes an alarm in
the zone. However, if the
fi
rst device is a manual call point, the double-knock zone immediately issues an alarm.
Double-knock zone prealarm timeout
It is possible to set the maximum prealarm time for the double-knock zones.
If a zone in prealarm state at the end of the set timeout has switched to stand-by state, the prealarm is automatically cleared.
If, however, the prealarm condition persists, the zone remains in prealarm state until the detector switches to stand-by or another
detector of the zone switches to alarm. The timeout can be set by steps of 5 minutes from 0 (in
fi
nite) to 60 minutes.
N.B.
The
Behavior after prealarm
setting can have an effect on the alarm release.
Prealarm
Alarm
No alarm
Alarm
Alarm
No alarm
Prealarm
Alarm
No alarm
Prealarm
Alarm
No alarm
SINGLE-KNOCK FIRE ZONE - ALARM TRIGGERING
The zone is in stand-by state
With one device in alarm state
the zone switches to alarm
One more device in alarm state triggers another alarm noti
fi
cation
SINGLE-KNOCK FIRE ZONE - PREALARM TRIGGERING
The zone is in stand-by state
With one device in prealarm state
the zone switches to prealarm
One more device in prealarm state
switches the zone to alarm and
triggers the alarm noti
fi
cations
DOUBLE-KNOCK FIRE ZONE - PREALARM TRIGGERING
The zone is in stand-by state
With one device in prealarm state
the zone switches to prealarm
One more device in prealarm state
switches the zone to alarm and
triggers the alarm noti
fi
cations
DOUBLE-KNOCK FIRE ZONE - ALARM TRIGGERING
The zone is in stand-by state
With one device in alarm state
the zone switches to prealarm
One more device in alarm state switches the zone to alarm
and triggers the alarm noti
fi
cations
Содержание Tecnofire TFA2-596
Страница 2: ...TFA2 596 TFA4 1192 2...
Страница 4: ...TFA2 596 TFA4 1192 4...
Страница 10: ...TFA2 596 TFA4 1192 10...
Страница 14: ...TFA2 596 TFA4 1192 14...
Страница 28: ...TFA2 596 TFA4 1192 28...
Страница 32: ...TFA2 596 TFA4 1192 32...
Страница 40: ...TFA2 596 TFA4 1192 40...
Страница 50: ...TFA2 596 TFA4 1192 50...
Страница 62: ...TFA2 596 TFA4 1192 62 NOTES...
Страница 63: ......