8-3 - Technical zones
Double-knock technical zone
The prealarm or alarm of a single device generates a technical prealarm in the zone, the intervention of a second device causes a
technical alarm in the zone.
Double-knock zone prealarm timeout
It is possible to set the maximum prealarm time for the double-knock zones. If a zone in prealarm state at the end of the set
timeout has switched to stand-by state, the prealarm is automatically cleared. If, however, the prealarm condition persists, the zone
remains in prealarm state until the detector switches to stand-by or another detector of the zone switches to alarm.
The timeout can be set by steps of 5 minutes from 0 (in
fi
nite) to 60 minutes.
N.B.
The
Behavior after prealarm
setting can have an effect on the alarm release.
The prealarm and alarm outputs of the technical zone must be programmed, specializing the programmable outputs for these
functions.
Single-knock technical zone
The alarm of a single device (single-knock) is enough to generate a technical alarm of the zone and trigger the output speci
fi
cally
programmed for technical alarm. If a device generates a prealarm, the zone will switch to prealarm state.
No alarm
No alarm
No alarm
No alarm
Technical prealarm
Technical prealarm
Technical prealarm
Technical alarm
Technical alarm
Technical alarm
Technical alarm
Technical alarm
SINGLE-KNOCK TECHNICAL ZONE - PREALARM TRIGGERING
The zone is in stand-by state
With one device in prealarm state
the zone switches to prealarm
One more device in prealarm state
switches the zone to alarm and triggers the alarm noti
fi
cations
SINGLE-KNOCK TECHNICAL ZONE - ALARM TRIGGERING
The zone is in stand-by state
With one device in alarm state
the zone switches to alarm
One more device in alarm state
triggers another alarm noti
fi
cation
DOUBLE-KNOCK TECHNICAL ZONE - PREALARM TRIGGERING
The zone is in stand-by state
With one device in alarm state
the zone switches to prealarm
One more device in prealarm state
switches the zone to alarm and triggers the alarm noti
fi
cations
DOUBLE-KNOCK TECHNICAL ZONE - ALARM TRIGGERING
The zone is in stand-by state
With one device in prealarm state
the zone switches to prealarm
One more device in prealarm state
switches the zone to alarm and triggers the alarm noti
fi
cations
Содержание Tecnofire TFA2-596
Страница 2: ...TFA2 596 TFA4 1192 2...
Страница 4: ...TFA2 596 TFA4 1192 4...
Страница 10: ...TFA2 596 TFA4 1192 10...
Страница 14: ...TFA2 596 TFA4 1192 14...
Страница 28: ...TFA2 596 TFA4 1192 28...
Страница 32: ...TFA2 596 TFA4 1192 32...
Страница 40: ...TFA2 596 TFA4 1192 40...
Страница 50: ...TFA2 596 TFA4 1192 50...
Страница 62: ...TFA2 596 TFA4 1192 62 NOTES...
Страница 63: ......