- 52 -
8.01 Overview
The WP20's RS232C and RS485 serial communications interfaces allow remote computers and
PLC’s to access RATE, TOTAL, SPEED, and Status data, in addition to requesting basic
calibration functions. The WP20 can be configured to send data either automatically (every 1/10
second fixed) or upon request (manually). If sending data automatically, only one unit can be
used per serial link. The automatic mode is commonly used for sending Rate and/or Total to
display devices. When requesting data manually, 16 units can be multi-dropped on one serial link
and each unit is identified using capital letters A to P. The characters used are ASCII. Wire the
serial communications per Section 4. Configure the Parameters per Section 6.02.41-45.
Note
: When setting up serial communications the message “FRAMING ERROR” might appear
in the MODE window. This indicates that a Parameter setting is incorrect. Assure that all serial
communications related Parameters are correct for the system -- Station ID, Parity, Baud Rate,
Command Menu, and Protocol (See Sections 6.02.41-45).
Important:
The plant remote equipment must also be operating with the exact same serial
communications settings (mutually compatible) for the system to operate properly.
8.02 Automatic Transmission
When a Command Menu Parameter (selected from the following table) other than 00 is entered
into the WP20, it will send the selected data automatically every 1/10 second. For example, if the
Command Menu is set to 04, the WP20 will transmit the RATE and TOTAL every 1/10 second.
Command
Data
Menu
Transmitted
00
(Used for manual data transmission only, see section 8.03)
01
RATE
02
TOTAL
03
SPEED
04
RATE,
TOTAL
05
RATE,
SPEED
06
Average
RATE
07
Average
SPEED
08
Average
RATE,
TOTAL
09
Average RATE, Average SPEED
10
Status
11
RATE,
Status
12
TOTAL,
Status
13
SPEED,
Status
14
RATE,
Status,
TOTAL
15
RATE,
Status,
SPEED
16
Average
RATE,
Status
17
Average
SPEED,
Status
18
Average
RATE,
Status,
TOTAL
19
Average RATE, Status, Average SPEED
20
Send RATE in FC20 set point mode. See FC20 manual.
CHAPTER 8 - SERIAL COMMUNICATIONS
Содержание Tecweigh 20
Страница 2: ... 1 ...
Страница 10: ... 9 2 09 I O Quick Reference Guide ...
Страница 20: ... 19 ...
Страница 24: ... 23 4 03 WY15 and WY25 Scale Wiring load cells ...
Страница 25: ... 24 4 04 HY15 and HY25 Field Wiring ...
Страница 26: ... 25 4 05 WY10 WY10HD and WY20 Scale Wiring LVDTs ...
Страница 27: ... 26 4 06 Chart Recorder Data Logger using the 4 20 ma output ...
Страница 28: ... 27 4 07 Chart Recorder Data Logger using the HFR output ...
Страница 29: ... 28 4 08 Remote Rate Total Display 4 09 Remote Tons Counter ...
Страница 30: ... 29 4 10 Radio Transceivers Local Scale Remote Processor ...
Страница 31: ... 30 4 11 Radio Transceivers Local Processor Remote PLC PC or Remote Display ...
Страница 32: ... 31 4 12 Radio Transceivers Local DC Generator Remote Processor ...
Страница 33: ... 32 4 13 Radio Transceivers Local DC Generator and Processor ...
Страница 34: ... 33 4 14 Multiple Processors to Tecweigh Multi Scale Display MSD ...
Страница 35: ... 34 4 15 Interposing Relay External 120 vac Power 4 16 Interposing Relay Internal 30 vdc Power ...
Страница 61: ... 60 SC300 PCB WY15 and WY25 SC400 PCB WY10 and WY20 ...
Страница 71: ... 70 10 01 WY10 Dimensions CHAPTER 10 DIMENSIONS ...
Страница 72: ... 71 10 02 WY10 HD Heavy Duty Dimensions ...
Страница 73: ... 72 10 03 WY15 Dimensions ...
Страница 74: ... 73 10 04 WY20 Dimensions ...
Страница 75: ... 74 10 05 WY25 Dimensions ...
Страница 76: ... 75 10 06 HY15 and 25 Dimensions ...