Techno GR F3S-TGR-SB-K2C-500 Series Скачать руководство пользователя страница 9

F3S-TGR-SBx-KxC series User’s 

manual 

 

 17

 

6 OPERATING 

PROCEDURES 

6.1 

SETTING THE INTERNAL DIP-SWITCHES 

• 

Disconnect the SLC’s power supply and remove the connector side 
of the transceiver, so that you can reach the two banks four-way 
dip-switches located there.

 

• 

Use a suitably sized screwdriver to set the dip-switches as per the 
required configuration according to the following tables.

 

 

6.1.1  SELECTION OF RESET MODE  

Single switch number 4 

Reset  

OFF Manual 
ON 

Automatic  (Initial setting) 

 

 
ATTENTION 

 
 
In every transceiver unit there are two separate dip-switch banks. The 
two banks must be set in the same way to get a valid configuration. 
 

Single switch number 3 

No function 

OFF DEFAULT 

SETTING 

ON NOT 

ALLOWED 

 
Dip switches number 1 and 2, act on the partial muting configuration. 
See “Partial muting configuration” chapter 7.3 on page after next. 

 

F3S-TGR-SBx-KxC series User’s 

manual 

 

 18

 

7  MUTING AND OVERRIDE FUNCTIONS 

7.1 GENERAL 

INFORMATION 

 

The 

muting 

and

 override 

functions

 

enable the SLC to be bypassed for 

operational requirements. As required by current standards, the SLC is 
provided with inputs for the activation of these functions. It should however be 
remembered that these functions basically override the system and they 
should therefore be used with due care. 

 

7.2 MUTING 

FUNCTION 

 

As mentioned in the introduction, the 

muting

 function can be enabled with any 

SLC by simply connecting the LMS muting indicator when the SLC is switched 
off. 
The presence of this indicator is recognised when the SLC is switched on. If 
its presence is detected, the SLC will enable the 

muting

 function and if it is not 

present the SLC will ignore any request for 

muting

It is important to note 

that if the 

muting

 indicator is connected when the SLC is already 

connected to the power supply, it will not be recognised and the 

muting

 

function will not be enabled.

 Once enabled, if the 

LMS muting

 indicator 

develops a fault or is removed without first disconnecting the SLC’s power 
supply, it will signal an error with the 

muting 

light, as described in section 10.  

 
To disable the 

muting

 function, the power supply must be turned on without 

the LMS muting indicator connected.

 

 
In brief: this function, present on all SLC s, is enabled and disabled by means 
of the following simple procedure: 

Disconnect the SLC’s power supply. 

Connect the appropriate 

LMS muting indicator

 and the muting 

sensors (see section 6)  

Restore the SLC’s power supply. 

Bypass the muting function as follows. 

Disconnect the SLC’s power supply. 

Disconnect the 

LMS muting indicator

 and the muting sensors (see 

section 6) 

Restore the SLC’s power supply. 

 
 

Содержание F3S-TGR-SB-K2C-500 Series

Страница 1: ...o it whenever necessary Do not open the housing or make any unauthorised modifications The power supply must be disconnected before proceeding with any external intervention Regulations and Standards...

Страница 2: ...with any standards codes or regulations that apply to the combination of products in the customer s application or use of the product At the customer s request TECHNO GR will provide applicable third...

Страница 3: ...2 2 2006 F3S TGR SBx KxC series User s manual 6 INDEX section page 1 OPERATION 7 2 PRECAUTIONS AND CRITERIA FOR INSTALLATION 8 2 1 CALCULATION OF THE MINIMUM DISTANCE FOR INSTALLATION 8 2 2 REFLECTING...

Страница 4: ...ator must be connected when the SLC is not connected to the power supply as shown in section 6 and then the SLC s power supply must be restored To disable the muting function the LMS muting indicator...

Страница 5: ...nearby surfaces Serious injuries can result if these effects are not taken into consideration Should there be any reflecting surfaces the distance must be sufficient to safeguard against passive refl...

Страница 6: ...n the opposite directions Staggered SLC1 Mirror2 SLC1 Mirror1 Mirror2 SLC2 Mirror1 SLC2 All these installation will prevent mutual interference between SLC F3S TGR SBx KxC series User s manual 12 Inse...

Страница 7: ...ves so the brackets d can be placed at an equal distance from each other Fixing facilities list 1 Movable nuts 8pcs 2 Fixing brackets 4pcs 3 Washer 8pcs 4 Grower 8pcs 5 Nut 8pcs F3S TGR SBx KxC series...

Страница 8: ...ety relay module Muting input A and Muting input B can be provided by mechanical switch photoelectric sensors proximities switch with closed contact in the presence of the object to be detected The te...

Страница 9: ...override the system and they should therefore be used with due care 7 2 MUTING FUNCTION As mentioned in the introduction the muting function can be enabled with any SLC by simply connecting the LMS m...

Страница 10: ...ng 1 Wiring must be done correctly 2 The muting sensors must recognise the whole length of the material i e pallets vehicles 3 The sensors must be arranged so that the material is also recognised if i...

Страница 11: ...Yellow 4 Muting input A Green 3 Input of A1 sensor Input of A2 sensor Input of B1 sensor Input of B2 sensor 24Vdc D a n g e r o u s z o n e F3S TGR SBx KxC series User s manual 22 Application with fo...

Страница 12: ...imum dimension of package that can cross the SLC D1 distance between muting actuator B and SLC It MUST be as short as possible Minimum distance allowable depends on the speed of conveyour the response...

Страница 13: ...time as long as the muting signals are valid Timing chart F ree Interrupted O N O F F O N O F F O N O F F A ctive O F F S LC O S S D M uting Input A M uting Input B M uting S tatus 0 03 sec Tm 3sec A...

Страница 14: ...5 seconds The override function is now enabled The LMS muting indicator flashes to signal the exclusion of the SLC The maximum duration of the override function is 120 seconds after which the SLC is r...

Страница 15: ...1 and 4 2 Check that it is not possible for a person to get between the SLC and the dangerous parts of the machinery Check that there is no external damage to the SLC and or to the external electrical...

Страница 16: ...SBx K3C 800 941 mm F3S TGR SBx K4C 900 1041 mm F3S TGR SBx KxC series User s manual 32 ITEM SPECIFICATION Materials Housing Front panel Sealing gasket Connector parts Powder coated aluminum Polycarbo...

Страница 17: ...Reverse polarity Overload Short circuit pulsed Input circuit Logical Zero level 0 8V Logical One level 14 24Vdc Input pulse duration Min 2 cycle time Response time 16ms Reset time TOFF TON interlock 3...

Страница 18: ...xC series User s manual 35 MODEL A B C D E L F3S TGR SBx K2C 500 500 514 614 F3S TGR SBx K3C 800 118 400 60 340 814 958 F3S TGR SBx K4C 900 118 300 300 300 914 1058 F3S TGR SBx KxC series User s manua...

Отзывы: