F3S-TGR-SBx-KxC series User’s 

manual 

 

 15

 

 

4.2 

NOTES ON CONNECTIONS 

 

• 

The transformer needed to power the system must comply with 
standard EN 60742 (dual isolation), or with equivalent isolation, 
e.g. VDE 0551. 

• 

The control unit must be protected with an external fuse, whose 
rated breaking current must be 1A. 

• 

The TEST/RESTART button must be located so that the 
operator can see the protected area when restarting

testing or 

overriding. 

• 

The external illuminated indicator for 

muting override 

enabled 

must be located so that it can be seen from all sides of 
operation. 

• 

Read the section on the 

muting

 function and its use before 

locating the sensors for the activation of this function. 

• 

Check that the load does not absorb current in excess of 
500mA; in this case a protection device will intervene to limit the 
maximum current. If loads with currents in excess of 500mA 
and up to 6A alternating current are to be controlled, please 
connect an external safety relay module.

 

• 

Muting input A and Muting input B can be provided by 
mechanical switch, photoelectric sensors, proximities switch,

 

with closed contact in the presence of the object to be detected. 

• 

The test connection must always be executed with a N.C. 
button or connected to an automatic device, such as a PLC. 

 
 

F3S-TGR-SBx-KxC series User’s 

manual 

 

 16

 

5 ALIGNMENT 

PROCEDURE 

 
After completing correct mechanical assembly and connections, as 
described in the previous sections, the SLC should be aligned as follows:  
 

• 

Disconnect the SLC’s power supply. 

• 

Open the 

test/restart 

contact. 

• 

Restore the SLC’s power supply. 

• 

Adjust the direction of the SLC by moving the transceiver or the 
mirror. The 2 yellow LEDs located on the transceiver will both be 
lit when the SLC is aligned correctly. In addiction also the green 
guard LED will switch on and the red break LED will switch off 

• 

After aligning the SLC, secure the bolts firmly. 

• 

Disconnect the power supply. 

• 

Restore the SLC’s power supply (with the 

test

 contact closed); it 

will enter operating mode. 

• 

Complete all the tests described in section 9 (final checks) and 
those required for routine maintenance (section 10). 

 
 
 

Содержание F3S-TGR-SB-K2C-500 Series

Страница 1: ...o it whenever necessary Do not open the housing or make any unauthorised modifications The power supply must be disconnected before proceeding with any external intervention Regulations and Standards...

Страница 2: ...with any standards codes or regulations that apply to the combination of products in the customer s application or use of the product At the customer s request TECHNO GR will provide applicable third...

Страница 3: ...2 2 2006 F3S TGR SBx KxC series User s manual 6 INDEX section page 1 OPERATION 7 2 PRECAUTIONS AND CRITERIA FOR INSTALLATION 8 2 1 CALCULATION OF THE MINIMUM DISTANCE FOR INSTALLATION 8 2 2 REFLECTING...

Страница 4: ...ator must be connected when the SLC is not connected to the power supply as shown in section 6 and then the SLC s power supply must be restored To disable the muting function the LMS muting indicator...

Страница 5: ...nearby surfaces Serious injuries can result if these effects are not taken into consideration Should there be any reflecting surfaces the distance must be sufficient to safeguard against passive refl...

Страница 6: ...n the opposite directions Staggered SLC1 Mirror2 SLC1 Mirror1 Mirror2 SLC2 Mirror1 SLC2 All these installation will prevent mutual interference between SLC F3S TGR SBx KxC series User s manual 12 Inse...

Страница 7: ...ves so the brackets d can be placed at an equal distance from each other Fixing facilities list 1 Movable nuts 8pcs 2 Fixing brackets 4pcs 3 Washer 8pcs 4 Grower 8pcs 5 Nut 8pcs F3S TGR SBx KxC series...

Страница 8: ...ety relay module Muting input A and Muting input B can be provided by mechanical switch photoelectric sensors proximities switch with closed contact in the presence of the object to be detected The te...

Страница 9: ...override the system and they should therefore be used with due care 7 2 MUTING FUNCTION As mentioned in the introduction the muting function can be enabled with any SLC by simply connecting the LMS m...

Страница 10: ...ng 1 Wiring must be done correctly 2 The muting sensors must recognise the whole length of the material i e pallets vehicles 3 The sensors must be arranged so that the material is also recognised if i...

Страница 11: ...Yellow 4 Muting input A Green 3 Input of A1 sensor Input of A2 sensor Input of B1 sensor Input of B2 sensor 24Vdc D a n g e r o u s z o n e F3S TGR SBx KxC series User s manual 22 Application with fo...

Страница 12: ...imum dimension of package that can cross the SLC D1 distance between muting actuator B and SLC It MUST be as short as possible Minimum distance allowable depends on the speed of conveyour the response...

Страница 13: ...time as long as the muting signals are valid Timing chart F ree Interrupted O N O F F O N O F F O N O F F A ctive O F F S LC O S S D M uting Input A M uting Input B M uting S tatus 0 03 sec Tm 3sec A...

Страница 14: ...5 seconds The override function is now enabled The LMS muting indicator flashes to signal the exclusion of the SLC The maximum duration of the override function is 120 seconds after which the SLC is r...

Страница 15: ...1 and 4 2 Check that it is not possible for a person to get between the SLC and the dangerous parts of the machinery Check that there is no external damage to the SLC and or to the external electrical...

Страница 16: ...SBx K3C 800 941 mm F3S TGR SBx K4C 900 1041 mm F3S TGR SBx KxC series User s manual 32 ITEM SPECIFICATION Materials Housing Front panel Sealing gasket Connector parts Powder coated aluminum Polycarbo...

Страница 17: ...Reverse polarity Overload Short circuit pulsed Input circuit Logical Zero level 0 8V Logical One level 14 24Vdc Input pulse duration Min 2 cycle time Response time 16ms Reset time TOFF TON interlock 3...

Страница 18: ...xC series User s manual 35 MODEL A B C D E L F3S TGR SBx K2C 500 500 514 614 F3S TGR SBx K3C 800 118 400 60 340 814 958 F3S TGR SBx K4C 900 118 300 300 300 914 1058 F3S TGR SBx KxC series User s manua...

Отзывы: