F3S-TGR-SBx-KxC series User’s
manual
23
Application with two sensors and single direction for material
exit:
This muting activation sequence is only available for SLCs
with postfix “
–MTL”
at the ordering code.
S B1 A1
D1 D2
D
Electrical connection of muting input
Muting input B (Yellow – 4)
Muting input A (Green – 3)
Input of A1 sensor
Input of B1 sensor
+24Vdc
D
a
n
g
e
r
o
u
s
z
o
n
e
F3S-TGR-SBx-KxC series User’s
manual
24
Where:
D: minimum dimension of package that can cross the SLC.
D1: distance between muting actuator B and SLC.
It MUST be as short as possible.
Minimum distance allowable depends on the speed of
conveyour, the response time of SLC and response time of
muting actuator.
D2: Distance between muting actuator A and muting actuator B.
It must be > 250mm
It also depends on the conveyour speed:
25 > d
max
[cm]= v[m/s] * 3[s] * 100
It is necessary that this distance does not allow both sensors to
be activated and thus
muting
if a person goes through by
accident.
Supply Cable
Cable to lamp
Muting cable
RX cable
TX cable
Muting
lamp
Start & Test
buttons
Protect
cables