34
Mod (Operating mode) - Par (Parameters)
The different operating modes refer
exclusively to mixer control and heating circuit
pump
. All others outputs are still controlled according to program and setting in all operating
modes. That concerns the standby function as well.
Automatic mode
„Aut”
Automatic mode switches over between normal heating mode and lowering mode due to
the time switch function. In parameter “
Par
” the application of the sensor
T6
(room sensor or
used in another way) must be set. Setting mode: Ho
ld “
Eingabe
”, change with “
ab/auf
” key.
Par
=
rAS
T6 is used as room sensor RAS
=
Std
T6 is no room sensor, frost protection function keeps active over T5
=
Unb
T6 is no room sensor, no frost protection function
Normal heating mode
„nor”
Normal heating mode continues. Time switch function has no influence to heating mode.
No lowering mode will be activated. No selection of parameters!
Lowering mode
„AbS”
In lowering mode the room temperature will be kept at the level set in adjustment “
Tabs
”.
No selection of parameters!
Party mode
„PAr”
Party mode keeps the room temperature at the level of normal heating mode. For this case
the time must be set in “
Par
”, at which the automatic mode should start again.
Note! “PAr” = Party operation mode, not to confuse with “Par” = Parameter
Holiday mode
„FEI”
When selecting this function and input of number of coming public holidays in “
Par
”, the
day of input will operate as Saturday and the specified number of days as Sundays. I.e. the
time switch function during these days complies with these of Saturday resp. Sunday. After
this time the function will be cancelled out of memory.
Vacation mode
„Url”
Setting the length of vacation
in days (in „
Par
“) the room temperature will be kept during
the vacation
at lowering temperature (“
Tabs
”). After this time the controller switches back to
automatic mode and the function is cancelled out of memory.
Standby mode
„Stb”
By setting standby mode the controller operates only in frost protection mode. When the
outdoor temperature
T5
decreases the frost protection thresho
ld set in “
Par
”, the heating
circuit operates in lowering mode.