Diagram 96:
Boiler (or buffer tank), hot water tank, 2 heating circuits
Sensors
Outputs
T1…. Boiler
A1…. Heating circuit pump 1
T2…. Heating circuit 2 return
A2…. Heating circuit pump 2
T3…. Tank bottom
A3…. Mixer open
T4…. Heating circuit 1 flow
A4…. Mixer close
T5…. Outdoor temperature
A5…. Tank feed pump
T6…. Room sensor
Basic function (P96):
Controlling of heating circuit pump
A1
,
A2
and hot water tank feed
pump
A5
: mixer control for heating circuit 1 (
A3&A4
); controlling of the second heating circuit
can be reached by absolute value control of pump speed control.
A1 = T1 > min1 & (heating = active)
A2 = T1 > min1 & T1 > T2 + diff1 & T2 < min2
A5 = T1 > min1 & T1 > T3 + diff2 & T3 < max
Required settings:
min1
…switch-on thresh. T1
A1,2 min2
…limit T2
A2
max
…limit tank bottom T3
A5
diff1
…boiler T1 – h.c.2 T2
A2 diff2
… boiler T1 – tk. bott. T3
A5
V
max
, V
min,
T+20, T-20, T
norm
, T
abs,
mixer control parameter Mr
heating pump parameter HPu, time program,
optionally: pump speed control Pd2 for heating circuit pump A2
A1 off
A2 off
A5 off
T1 < min1 T1 < min1 T1 < min1
diff1 diff2
A1 on
A2
on
A5 on
Switch-off cond. HPu T2 > min2 T3 > max
A1 off
A2 off A5 off