49
Pump speed control Pd1, Pd2
This menu allows activating and adjustment the outputs A1 and A2 for pump speed con-
trol.
Decrease of flow, e.g. in a boiler, causes
– because of the longer dwell time in it – an in-
crease of output temperature. So it is possible to get the boiler and the tank as well to a
useable temperature level in short time, but that causes a worse efficiency.
The sensor creates together with controller, pump and the hydraulic system a control loop,
which makes it possible to keep the temperature at the sensor constant by speed variation.
Three control functions are available; they can be activated together:
Absolute value control
– Maintaining a sensor at constant temperature
Differential control
- Keeps the temperature constant between two sensors
Event control
- If a set temperature event occurs, the speed control starts, thus keeping
a sensor constant.
Advice:
Differential control and event control allow setting the temperature sensor
T7
. In
this case
T7
means nominal flow temperature
Vsoll
.
Setting of pump speed control for output A1
Absolute value control
2 sec
2 sec
short
A
= Absolute value control
Temperature sensor, whose
temperature is kept constant at
the absolute value
C
(
T1
)
ew
= 0
Value is changeable from - 6 to 6; negative sign means
inverse function => increasing temperature causes de-
creasing speed. A0 = off
Setting desired temperature C