52
Pulse input
Inputs
7 - 8
can detect pulses with
max. 20 Hz.
Inputs
1 - 6
can detect pulses with max.
10 Hz
and
at least
50 ms
pulse duration.
Select the measured variable
Wind speed
A quotient must be entered for the "Wind speed" measured variable. This is the signal frequency at
1 km/h.
Example: The WIS01 wind sensor issues one pulse (=1Hz) per second at a wind speed of 20 km/h.
Therefore the frequency at 1 km/h equals 0.05 Hz.
Setting range: 0.01 – 1.00 Hz
Flow rate
A quotient must be entered for the "Flow rate" measured variable. This is the flow rate in litres per
pulse.
Setting range: 0.1 – 100.0 l/pulse
Pulse
This measured variable is used as the input variable for the "Meter/Counter" function, as a pulse
counter with "Pulses" as its unit.
User defined
For the "User defined" measured variable, both the quotient and the unit must be entered.
Setting range for quotient: 0.00001 – 1000.00000 units/pulse (5 decimal places)
Units: l, kW, km, m, mm, m³.
For l, mm and m³ the unit of time must be selected as well. For km and m the units of time are pre
-
defined and cannot be changed.
Example: For the "Energy meter" function, the unit "kW" can be used. In the example above, 0.00125
kWh/pulse was selected, which equates to 800 pulses /kWh.