69
CAN digital inputs
Up to 64 CAN digital inputs can be programmed. They are defined by specifying the transmission
node number and the number of the transmission node's CAN output.
Their parameters are programmed in almost exactly the same way as for the CAN analogue inputs.
Under Measured variable / User the Display for the CAN digital input can be changed from Off / On
to No / Yes and you can define whether the controller should issue the last status transmitted ("Un
-
changed") or a definable substitute status when the timeout time is exceeded.
CAN analogue outputs
Up to 32 CAN analogue outputs can be programmed. They are defined by specifying the source in
the controller.
Specify the source in the controller which supplies the value for the CAN output.
Example:
Source, Input 1
• Inputs
• System values
• Functions
• DL bus
• Fixed values