50
Inputs
The energy meter has 8 inputs for analogue (measurements), digital (ON/OFF) signals or pulses.
This menu displays the inputs with their designation and the current measurements or status.
Example
of a programmed system; input 4 is still unused:
Programming the parameters
Sensor type and measured variable
Once the required input is selected, the sensor type can be defined.
First, you must specify the basic type of input signal.
• Digital
• Analogue
• Pulse
Typ
S1
S2
S3
S4
S5
S6
S7
S8
VT1
VT2
VT1
VT2
Digital
x
x
x
x
x
x
x
x
Analogue
(all measured
variables and sensor
types)
x
x
x
x
x
x
Analogue
(measured
variable: temp.; sensor:
FTS)
x
x
Pulse
(all measured vari
-
ables) (e.g. VSG sensor)
S0 signals (max 20 Hz)
x
x
Pulse
(measured varia
-
ble: flow rate)
x
x