4. REFRIGERANT FLOW DIAGRAM
8
Indoor Unit KPA128R5
Outdoor Unit GR128R5
Compressor
4-way
valve
Accumulator
Wide tube
service
valve
Wide tube
O.D.
ø12.7 mm
(1/2 ")
Narrow
tube
service
valve
Narrow tube
O.D.
ø6.35 mm
(1/4")
Heat exchanger
Heat exchanger
Muffler
Capillary tube
Capillary tube
Cooling cycle
Heating cycle
Strainer
Indoor unit Outdoor unit
Strainer
Check
valve
Wide tube
Thickness:
Min. 8 mm
Insulation
Narrow tube
Thickness:
Min. 8 mm
Insulation of Refrigerant Tubing
Because capillary tubing is used in the outdoor unit, both the
wide and narrow tubes of this air conditioner become cold. To
prevent heat loss and wet floors due to dripping of
condensation, both tubes must be well insulated with a
proper insulation material. The thickness of the insulation
should be a min. 8 mm.
IMPORTANT
CAUTION