14
6. ELECTRICAL DATA
6-1. Electrical Characteristics
Indoor Unit KPA128R5
Outdoor Unit GR128R5
COOLING
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at 220 – 240V ~ 50Hz
Rating Conditions Running Amps. A 0.28 /
0.29 0.30
/
0.32 5.3 / 5.4 5.9 / 6.0
Power Input kW 0.060 / 0.070 0.066 / 0.076 1.13 /
1.18 1.26 /
1.33
Full Load Conditions Running Amps. A 0.28 /
0.29 0.30
/
0.32 6.8 / 6.6 7.4 / 7.2
Power Input kW 0.060 / 0.070 0.066 / 0.076 1.43 /
1.46 1.56 /
1.61
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
HEATING
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at 220 – 240V ~ 50Hz
Rating Conditions Running Amps. A 0.28 /
0.29 0.30
/
0.32 5.5 / 5.6 6.1 / 6.2
Power Input kW 0.060 / 0.070 0.066 / 0.076 1.17 /
1.22 1.30 /
1.37
Full Load Conditions Running Amps. A 0.28 /
0.29 0.30
/
0.32 8.0 / 7.7 8.6 / 8.3
Power Input kW 0.060 / 0.070 0.066 / 0.076 1.71 /
1.68 1.84 /
1.83
Rating Conditions : Indoor Air Temperature 20°C D.B.
Outdoor Air Temperature 7°C D.B. / 6°C W.B.
Full Load Conditions : Indoor Air Temperature 27°C D.B.
Outdoor Air Temperature 24°C D.B. / 18°C W.B.