10 11 294 F.GB.I.E.D.01
37.4163.129.1 06/97
DECLARATION OF CONFORMITY
This product is marked as it satisfies Directives:
– Low voltage no. 73/23 EEC and 93/68 EEC.
– Electromagnetic compatibility no. 89/336 ECC, 92/31 EEC
and 93/68 EEC.
This declaration will become void in case of of misusage
and/or non observance though partial of manufacturer's
installation and/or operating instructions.
COOLING ONLY MODELS
OPERATING LIMITS
L
Maximum conditions
Outdoor temperature :
52°C D.B.*
Room temperature
:
35°C D.B. / 22.5°C W.B.
L
Minimum conditions
Outdoor temperature :
19°C D.B.**
Room temperature
:
19°C D.B. / 14°C W.B.
HEAT PUMP MODELS
OPERATING LIMITS
L
Cooling Maximum conditions
Outdoor temperature :
46°C D.B.
Room temperature
:
35°C D.B. / 22°C W.B.
L
Cooling Minimum conditions
Outdoor temperature :
19°C D.B.
Room temperature
:
19°C D.B. / 14°C W.B.
L
Heating Maximum conditions
Outdoor temperature :
24°C D.B. / 18°C W.B.
Room temperature
:
27°C D.B.
L
Heating Minimum conditions
Outdoor temperature :
–8°C D.B. / –9°C W.B.
Power Supply:
220 - 240 V ~ 50 Hz
Tools required for installation (not supplied)
1
1. Standard screwdriver
1
2. Phillips head screwdriver
1
3. Knife or wire stripper
1
4. Tape measure
1
5. Level
1
6. Sabre saw or key hole saw
1
7. Hacksaw
1
8. Core bits ø 5
1
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for reburring)
EG
I
F
D
E
Model Combinations
Combine indoor and outdoor units only as listed below.
COOLING ONLY MODELS
Indoor Units
Outdoor Units
KA96C5
GR93C5
KA127C5
GR125C5
HEAT PUMP MODELS
KA96R5
GR95R5
KA127R5
GR124R5
HEX
1
WRENCH
REMOTE
1
CONTROL UNIT
ACCESSORIES SUPPLIED WITH THE UNIT
PARTS
FIGURE
Q.TY
PARTS
FIGURE
Q.TY
PARTS
FIGURE
Q.TY
RAWL PLUG
3
PLASTIC
1
COVER
REMOTE CONTROL
1
UNIT SCREW
AAA ALKALINE
2
BATTERY
DRAIN
1
ELBOW
*
TAPPING
4
SCREW 4x30
*
Available only for heat pump models.
WASHER
2
BRACKET
1
INSULATING MATERIAL
FOR INDOOR UNIT
2
CONNECTIONS
CLAMPER
6
INSTALLATION INSTRUCTIONS
- Split system air conditioner -
A-TECHNIBEL.KA 11-06-1997 14:15 Pagina 1