background image

2.  Place and Space for Installation

Choose a place as cool as possible.  The place
should be well ventilated, and the intake air should
not be hotter than the outside temperature.  (max.
45 °C)

Avoid the vicinity of heat sources, exhaust fans,
etc. (Fig. 2-1)

Required space around the outdoor unit for free air
flow and servicing is given in Fig. 2-2.

When using the Dual System Kit, be sure to keep a
separation of 25 cm as minimum between the air
intake of the outdoor unit (rear surface) and wall or
fence for maintenance work.

To avoid the effects of humidity and ground moisture,
the unit should be placed on concrete blocks or slab
at least 10 cm high above ground level. (Fig. 2-3)

The unit must be level and be anchored securely to its
base with anchor bolts or the like. An unsteady
foundation will cause abnormal noise and vibration.
(Fig. 2-3)

Depending on the ambient temperature during
operation of the outdoor unit, the dews may
adhere or may  be frozen onto the service valves.
When the outdoor unit is to be installed in a place
where these dew drops may cause some
problem, provide the heat insulation for the
service valves or provide a plate under the
service valves to receive the dew drops.

3

CAUTION

!

Fig. 2-1

Hot air

Exhaust fan

Heat source

Outdoor unit

Air intake

Min. 15 cm

Air discharge

Min. 
50 cm

Valve
side
Min. 
60 cm

Min. 
15 cm

Obstacle above

Ground

2 m

2 m

Air discharge

Obstacle

Fig. 2-2

Min.
10 cm

Fig. 2-3

NOTE

Содержание DKR8585C

Страница 1: ...0M3C5TA MCAV92C5TA CAV92C5TA x 4 DKR8585C For details of its installation refer to the instruction manual of DKR8585C e e h h h h h h e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e...

Страница 2: ...ting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing ln a Ceiling Wall or Floor Make sure the ceiling wall floor is strong e...

Страница 3: ...ing length of C 25 g m is longer than 7 5 m No additional charge of compressor oil is required 2 English 1 Selection of Installation Site Maximum Allowable Tubing Length L and Elevation Difference H F...

Страница 4: ...e blocks or slab at least 10 cm high above ground level Fig 2 3 The unit must be level and be anchored securely to its base with anchor bolts or the like An unsteady foundation will cause abnormal noi...

Страница 5: ...o provide a minimum space of 50 cm between the air discharge outlet and a nearby obstacle The air discharge faces a sidewalk and hot air will be directed toward passersby Figs 2 4 and 2 5 4 English Fi...

Страница 6: ...ust be grounded Units A B MCAV92 CAV92 Unit C MCAV KPAV180 5 WARNING AWG American Wire Gauge A Power Supply Line Length m B Inter Line Length m Fuse or Cross Sectional Area Circuit Capacity 3 5 mm2 5...

Страница 7: ...2 Air conditioner will not operate Problem 3 Compressor will not start only indoor unit will operate English CAUTION 1 2 4 A 4 5 6 2 4 5 1 8 2 1 Grounding line or or Indoor unit Outdoor unit 1 2 4 B...

Страница 8: ...the solid wire to form a loop suitable for the terminal screw 4 Shape the loop wire properly place it on the terminal plate and fix it securely with the removed terminal screw using a screwdriver For...

Страница 9: ...be sure to mount it on the copper tube d Make a flare at the end of copper tube with a flare tool Fig 4 3 Use RIGID or equivalent A good flare should have the following characteristics inside surface...

Страница 10: ...en up the union connection portion of the indoor unit using a double spanner Fig 7 1 Connect both the wide and narrow tubes of the outdoor unit Fig 7 2 When using the torque wrench be sure to apply th...

Страница 11: ...ing nitrogen gas or outdoor unit s gas according to the installation site conditions The respective procedures are described below 1 Using Nitrogen Gas Unit A a Leak test 1 With the service valves on...

Страница 12: ...m pump The operation time for the vacuum pump varies with tubing length and capacity of the pump The following table shows the amount of time for evacuation Note The rquired time in the above table is...

Страница 13: ...onnet and flare nut on the wide tube service port and fasten the flare nut securely with an adjustable wrench or box wrench Next mount the valve cap and tighten it with a torque wrench the cap needs t...

Страница 14: ...ated based on the assumption that the ideal or target vacuum condition is around 10 mmHg abs 3 With the vacuum pump still running close the Lo knob of the manifold valve Then stop the vacuum pump Be s...

Страница 15: ...connected to the wide tube service port Then remove the hose 4 Replace the bonnet and flare nut on the wide tube service port and fasten the flare nut securely with an adjustable wrench or box wrench...

Страница 16: ...shifts into cooling operation and cool air will start to be felt Cooling operation with the switch at the TEST position is unaffected by the room temperature 4 After stopping the test run turn the op...

Страница 17: ...down in cooling operation 1 Connect a low pressure gauge manifold hose to the charge port on the wide tube service valve 2 Lower the stem of the wide tube service valve to position c and purge the air...

Страница 18: ...ut prior notice Per garantire un costante miglioramento dei nostri prodotti ci riserviamo di modificarli senza preavviso Par souci d am lioration constante nos produits peuvent tre modifi s sans pr av...

Отзывы: