b)  Leak test

(1) After confirming the power is off, disconnect the

connector (GRN) (between timer and terminal 5)
to separate A and B parts. (Fig. 8-4 )  Then
connect part A of this connector (GRN) with the
connector C (BLU) and turn on the power
source. (Fig. 8-5 )

(2) With the hexagonal wrench, turn the valve stem

on the narrow tube service valve
counterclockwise by 90 degrees (1/4 turn) for
10 seconds, and then turn the stem clockwise
to close it again. (Fig. 8-6)

(3) Leak test all joints at the tubing (both indoor

and outdoors) with liquid soap.  Bubbles
indicate a leak.  Be sure to wipe off the soap
with a clean cloth.

c)  Finishing job

(1) With the hexagonal wrench, turn the wide tube

service valve stem counterclockwise to fully
open the valve.

(2) Turn the narrow tube service valve stem

counterclockwise to fully open the valve.

(3) Loosen the vacuum hose connected to the

wide tube service port.  Then, remove the hose.

(4) Replace the bonnet and flare nut on the wide

tube service port and fasten the flare nut
securely with an adjustable wrench or box
wrench.  Next, mount the valve cap and tighten
it with a torque wrench (the cap needs to be
tightened with the torque of 200 kg-cm).
This process is very important to prevent
gas from leaking from the system.

(5) Turn off the power source.

(6) Connect parts A and B of the connector

(GRN) as original state. (Fig. 8-4)

To air purge unit C, perform steps (2) and (3) of 
b) Leak test and then steps (1) to (4) of c) Finishing
job in order.

This completes air purge with a vacuum pump.  The
air conditioner is now ready to test run.

(To be continued to page 15)

14

English

Be sure to completely insert
the hex wrench before
attempting to turn the valve.

CAUTION

!

NOTE

4

2

1

3

8

6

5

7

1

BLU

B

A

GRN

C

TERMINAL 8P

OUTDOOR UNIT

2

3

4

5

TERMINAL 5P

Fig. 8-4

Fig. 8-5

Fig. 8-6

Hex wrench

Narrow tube

Wide tube

Vacuum
hose to
manifold
value

Valve cap

90°(1/4 turn)

GRN (A)

BLU (C)

Содержание DKR8585C

Страница 1: ...0M3C5TA MCAV92C5TA CAV92C5TA x 4 DKR8585C For details of its installation refer to the instruction manual of DKR8585C e e h h h h h h e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e...

Страница 2: ...ting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing ln a Ceiling Wall or Floor Make sure the ceiling wall floor is strong e...

Страница 3: ...ing length of C 25 g m is longer than 7 5 m No additional charge of compressor oil is required 2 English 1 Selection of Installation Site Maximum Allowable Tubing Length L and Elevation Difference H F...

Страница 4: ...e blocks or slab at least 10 cm high above ground level Fig 2 3 The unit must be level and be anchored securely to its base with anchor bolts or the like An unsteady foundation will cause abnormal noi...

Страница 5: ...o provide a minimum space of 50 cm between the air discharge outlet and a nearby obstacle The air discharge faces a sidewalk and hot air will be directed toward passersby Figs 2 4 and 2 5 4 English Fi...

Страница 6: ...ust be grounded Units A B MCAV92 CAV92 Unit C MCAV KPAV180 5 WARNING AWG American Wire Gauge A Power Supply Line Length m B Inter Line Length m Fuse or Cross Sectional Area Circuit Capacity 3 5 mm2 5...

Страница 7: ...2 Air conditioner will not operate Problem 3 Compressor will not start only indoor unit will operate English CAUTION 1 2 4 A 4 5 6 2 4 5 1 8 2 1 Grounding line or or Indoor unit Outdoor unit 1 2 4 B...

Страница 8: ...the solid wire to form a loop suitable for the terminal screw 4 Shape the loop wire properly place it on the terminal plate and fix it securely with the removed terminal screw using a screwdriver For...

Страница 9: ...be sure to mount it on the copper tube d Make a flare at the end of copper tube with a flare tool Fig 4 3 Use RIGID or equivalent A good flare should have the following characteristics inside surface...

Страница 10: ...en up the union connection portion of the indoor unit using a double spanner Fig 7 1 Connect both the wide and narrow tubes of the outdoor unit Fig 7 2 When using the torque wrench be sure to apply th...

Страница 11: ...ing nitrogen gas or outdoor unit s gas according to the installation site conditions The respective procedures are described below 1 Using Nitrogen Gas Unit A a Leak test 1 With the service valves on...

Страница 12: ...m pump The operation time for the vacuum pump varies with tubing length and capacity of the pump The following table shows the amount of time for evacuation Note The rquired time in the above table is...

Страница 13: ...onnet and flare nut on the wide tube service port and fasten the flare nut securely with an adjustable wrench or box wrench Next mount the valve cap and tighten it with a torque wrench the cap needs t...

Страница 14: ...ated based on the assumption that the ideal or target vacuum condition is around 10 mmHg abs 3 With the vacuum pump still running close the Lo knob of the manifold valve Then stop the vacuum pump Be s...

Страница 15: ...connected to the wide tube service port Then remove the hose 4 Replace the bonnet and flare nut on the wide tube service port and fasten the flare nut securely with an adjustable wrench or box wrench...

Страница 16: ...shifts into cooling operation and cool air will start to be felt Cooling operation with the switch at the TEST position is unaffected by the room temperature 4 After stopping the test run turn the op...

Страница 17: ...down in cooling operation 1 Connect a low pressure gauge manifold hose to the charge port on the wide tube service valve 2 Lower the stem of the wide tube service valve to position c and purge the air...

Страница 18: ...ut prior notice Per garantire un costante miglioramento dei nostri prodotti ci riserviamo di modificarli senza preavviso Par souci d am lioration constante nos produits peuvent tre modifi s sans pr av...

Отзывы: