background image

9

5. Insulation of Refrigerant Tubing

This outdoor unit uses a system of capillary tubes, which cause
both the wide and narrow tubes to become cold.

To prevent heat loss and condensation, these tubes must be
adequately insulated.  Thickness of the insulation material should
be a minimum of 8 mm.

Insulation Material

The insulation material must have good insulating characteristics,
must be easy to use, be age resistant, and must not easily absorb
moisture. Either polyethylene or foam rubber insulation is
recommended.

When applying the insulation, first connect the refrigerant tubing to
the outdoor unit.  After performing a leak test on the connecting
part, insulate it, then wrap it with vinyl masking tape.

6. Tubing to be Used

Deoxidized annealed copper tube must be used for the refrigerant
tubing. The diameter and thickness are listed in Table 3.

Table 3

7. Tubing Connection

Tighten up the union connection portion of the indoor unit using 
a double spanner. (Fig. 7-1)

Connect both the wide and narrow tubes of the outdoor unit. 
(Fig. 7-2)

When using the torque wrench, be sure to apply the correct torque
according to the tubing diameter as given in Table 4.

Table 4

Fig. 7-1

Indoor unit

Outdoor unit

Fix

Torque wrench

Tubing Diameter

Tightening Torque

6.35 mm

Approx. 150 – 200 kg-cm

9.52 mm 

Approx. 350 – 400 kg-cm

12.7 mm 

Approx. 500 – 550 kg-cm

Combination

Narrow Tubing

Wide Tubing

Outdoor unit

Indoor unit

Outer Dia.

Thickness

Outer Dia.

Thickness

GRV340

MCAV92/CAV92

                     6.35 mm 0.8 mm 9.52 mm 0.8 mm

MCAV/KPAV180               6.35 mm 0.8 mm 12.7 mm 0.8 mm

min. 
8 mm

Fig. 5-1

Insulation

Thickness:
min. 8mm

Min.
8mm

CAUTION

!

After a tube has
been insulated,
never try to bend it
into a narrow
curve, as this may
cause the tube to
break or crack.

Insulation

Fig. 5-2

NOTE

Unit A, B ........ MCAV92/CAV92

Unit C ............. MCAV/KPAV180

Fig. 7-2

Narrow
tube

Wide tube

Unit A

Narrow
tube

Wide tube

Unit B

Wide tube

Narrow
tube

*Capi box

Unit C

* Remove this capi box when installing the

optional Dual System Kit (DKR8585C).

Содержание DKR8585C

Страница 1: ...0M3C5TA MCAV92C5TA CAV92C5TA x 4 DKR8585C For details of its installation refer to the instruction manual of DKR8585C e e h h h h h h e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e...

Страница 2: ...ting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing ln a Ceiling Wall or Floor Make sure the ceiling wall floor is strong e...

Страница 3: ...ing length of C 25 g m is longer than 7 5 m No additional charge of compressor oil is required 2 English 1 Selection of Installation Site Maximum Allowable Tubing Length L and Elevation Difference H F...

Страница 4: ...e blocks or slab at least 10 cm high above ground level Fig 2 3 The unit must be level and be anchored securely to its base with anchor bolts or the like An unsteady foundation will cause abnormal noi...

Страница 5: ...o provide a minimum space of 50 cm between the air discharge outlet and a nearby obstacle The air discharge faces a sidewalk and hot air will be directed toward passersby Figs 2 4 and 2 5 4 English Fi...

Страница 6: ...ust be grounded Units A B MCAV92 CAV92 Unit C MCAV KPAV180 5 WARNING AWG American Wire Gauge A Power Supply Line Length m B Inter Line Length m Fuse or Cross Sectional Area Circuit Capacity 3 5 mm2 5...

Страница 7: ...2 Air conditioner will not operate Problem 3 Compressor will not start only indoor unit will operate English CAUTION 1 2 4 A 4 5 6 2 4 5 1 8 2 1 Grounding line or or Indoor unit Outdoor unit 1 2 4 B...

Страница 8: ...the solid wire to form a loop suitable for the terminal screw 4 Shape the loop wire properly place it on the terminal plate and fix it securely with the removed terminal screw using a screwdriver For...

Страница 9: ...be sure to mount it on the copper tube d Make a flare at the end of copper tube with a flare tool Fig 4 3 Use RIGID or equivalent A good flare should have the following characteristics inside surface...

Страница 10: ...en up the union connection portion of the indoor unit using a double spanner Fig 7 1 Connect both the wide and narrow tubes of the outdoor unit Fig 7 2 When using the torque wrench be sure to apply th...

Страница 11: ...ing nitrogen gas or outdoor unit s gas according to the installation site conditions The respective procedures are described below 1 Using Nitrogen Gas Unit A a Leak test 1 With the service valves on...

Страница 12: ...m pump The operation time for the vacuum pump varies with tubing length and capacity of the pump The following table shows the amount of time for evacuation Note The rquired time in the above table is...

Страница 13: ...onnet and flare nut on the wide tube service port and fasten the flare nut securely with an adjustable wrench or box wrench Next mount the valve cap and tighten it with a torque wrench the cap needs t...

Страница 14: ...ated based on the assumption that the ideal or target vacuum condition is around 10 mmHg abs 3 With the vacuum pump still running close the Lo knob of the manifold valve Then stop the vacuum pump Be s...

Страница 15: ...connected to the wide tube service port Then remove the hose 4 Replace the bonnet and flare nut on the wide tube service port and fasten the flare nut securely with an adjustable wrench or box wrench...

Страница 16: ...shifts into cooling operation and cool air will start to be felt Cooling operation with the switch at the TEST position is unaffected by the room temperature 4 After stopping the test run turn the op...

Страница 17: ...down in cooling operation 1 Connect a low pressure gauge manifold hose to the charge port on the wide tube service valve 2 Lower the stem of the wide tube service valve to position c and purge the air...

Страница 18: ...ut prior notice Per garantire un costante miglioramento dei nostri prodotti ci riserviamo di modificarli senza preavviso Par souci d am lioration constante nos produits peuvent tre modifi s sans pr av...

Отзывы: