TECH
However, if the temperature continues to drop, the controller will activate
the feeder and the fan at 60°C and it will continue to operate until the
water heater setpoint temperature is reached.
VI.5.Temperature Protection
The regulator features an additional protection in case the bimetal
sensor is damaged. After the temperature exceeds 95°C, the alarm is
sounded. The display shows:
Temperature Too High
The current temperature is read from an electronic sensor and processed
by the thermoregulator. When the alarm temperature is exceeded, the
fan is shut off and both pumps begin to run in order to distribute hot
consumption water throughout the system.
VI.6.Fuel Container Protection
At the fuel container screw, an additional temperature sensor is
mounted. If the temperature rise is high (above 70°C), the alarm is
sounded: the feeder is activated for 3 minutes with the fuel being moved
into the combustion chamber. The screw sensor protects the fuel from
being combusted in the grate.
VI.7.Fuse
The regulator features two WT 6.3A tube fuses to protect the
network.
ATTENTION:
it is not advisable to use fuses with higher current ratings.
Higher current ratings may cause damage to the controller.
-25-
Содержание ST-45
Страница 1: ...ST 44 USER S MANUAL...
Страница 31: ...TECH 31...
Страница 32: ...ST 45 User s Manual 32...