ST-401N User's Manual v 1.0.3 

6

 - 

IV.c.3) Holiday Mode 

After the user activates Holiday Mode, the pump operates when one of the following conditions is met: 
The  collector's  temperature  increases  to  the  overheat  temperature  value  (SERVICE  MENU>  Solar 
Collector  >  Overheat  Temperature)  reduced  by  the  value  of  the  parameter  Delta  Holiday  (SERVICE 
MENU> Solar Collector > Delta Holiday). When this condition is met, the pump is activated to cool down 
the collector. The pump is deactivated after the temperature is reduced by 5°C. 
 If the  collector's temperature is lower than the tank's temperature  – the pump is activated to cool 
down the tank and will operate until the collector's and the tank's temperatures are level. 
 

IV.c.4) Anti-Legionella 

This function is only active when an additional device is connected (found under the function Peripherals 
in the Service Menu and then activated). Thermal disinfection involves increasing the temperature to 
the required disinfection temperature in the tank – this reading is taken from the upper sensor in the 
tank (in the case of using an optional sensor, the user should make sure that this sensor measures the 
temperature in the upper part of the tank because this is the priority sensor for this function). This is 
to eliminate the Legionella pneumophila bacteria that reduce the body's cell immunity. These bacteria 
often multiply in tanks with stagnant hot water (at an optimum temperature of 35°C). After the user 
activates this function, the tank heats up to the defined temperature (SERVICE MENU > Peripherals > 
Heater  >  Anti-Legionella  >  Anti-Legionella  Temperature
)  and  maintains  such  a  temperature  for  the 
time of disinfection (SERVICE MENU > Peripherals > Heater > Anti-Legionella > Anti-Legionella Time
and then returns to the regular operation mode. 
From the moment of activating the disinfection, the temperature of disinfection needs to be reached in 
no longer than the time defined by the user (SERVICE MENU > Peripherals > Heater > Anti-Legionella 
> Maximum Anti-Legionella Time
), otherwise this function is deactivated automatically. 
 

IV.c.5) Manual Operation 

Using this function, the user may manually (by pressing the ‘Menu’ button) activate and deactivate the 
following to control the installation's equipment: 
- Solar Pump, 
- Second Solar Pump or Switching Valve, 
- Peripherals - Additional Device (voltage-free contact e.g. for firing up the pellet boiler). 

 

IV.d) Timer 

Using this function, the user adjusts the current hour for regulator operation. 
 

IV.e) Date 

Using  this  function,  the  user  adjusts  the  current  date.  The  correct  adjustment  of  date  and  hour  is 
necessary to calculate energy in a proper manner. 

 

IV.f) Ethernet Module 

 
NOTE   

Control of this type is possible after purchasing and connecting an additional  ST-500 control module 
(which is not added to the controller as a standard). 
 

The Ethernet Module is a device for enabling remote control over the collector's operation via 

the Internet or a local network. On the home computer screen, the user controls the status of all the 
solar installation devices and the operation of each device is presented in the form of an animation. 
 

After activating the Internet module and selecting the DHCP option, the controller automatically 

downloads the following parameters from the local network: IP Address, IP Mask, Gateway Address and 
DNS Address. In the case of any problems with downloading the network parameters, it is possible to 
adjust these parameters manually. The method of obtaining the local network's parameters is described 
in the manual for the Internet Module. 
 

The function Reset Module Password may be used when the user  changed the factory user's 

password to his own password on the login page. When the new password is lost, it is possible to return 
to the factory password after resetting the module password. 
 
 

Содержание ST-401N PWM

Страница 1: ...Tech 1 User s manual ST 401N PWM...

Страница 2: ...ure the regulator is disconnected from the mains before perform ing any activities involving the power supply plugging cables installing the device etc The device should be installed by a qualified el...

Страница 3: ...l signal relay is necessary to control the heater III Principle Of operation Description of the Control Panel of a Sample System Opis panelu steruj cego przyk adowego uk adu The regulator is controlle...

Страница 4: ...Active Operation Mode The Symbol of Active Additional Device Peripherals Automatic Operation Mode Circulation Pump Collector Defrosting Mode Firing up the Pellet Boiler voltage free signal Holiday Mo...

Страница 5: ...VICE MENU Pumps Solar Pump Deactivation Delta in this case the pump will be activated again when the temperature on the collector increases above the tank s temperature by the Solar Pump Activation De...

Страница 6: ...of activating the disinfection the temperature of disinfection needs to be reached in no longer than the time defined by the user SERVICE MENU Peripherals Heater Anti Legionella Maximum Anti Legionel...

Страница 7: ...ction of property IV h Statistics The parameters in this submenu allow the user to monitor the current conditions of the controller s operation IV h 1 Gain This parameter allows the user to monitor th...

Страница 8: ...essing the Menu button In order to return to the display s main view exit the service menu the user should use the Exit button by pressing it several times or waiting for approx 30 seconds the device...

Страница 9: ...m Reheating Temperature Alarm Hysteresis Defrosting Time Anti Freeze Temperature Collector Delta Pumps Regulated Revolutions Collector Maximum Temperature Solar Pump Deactivation Delta Solar Pump Acti...

Страница 10: ...oo hot in the container the Cooling Down to Set Value function should be started After activating this option when the collector s temperature drops below that of the container the pump is activated i...

Страница 11: ...ng the user declares the value of the collector s maximum alarm temperature when the pump may be damaged This temperature should be adjusted according to the collector s technical data Due to phenomen...

Страница 12: ...mpling aimed at updating the temperature reading consisting in a short activation of the collector s pump when normal conditions for the pump s activation are not met Sampling requires a short activat...

Страница 13: ...vate the heater Then the user selects the time interval in which the electric heating function will be active by means of the From and To functions V f 4 Contact not Consistent with Pump This setting...

Страница 14: ...vated and the following symbol will appear on the right hand side of the display An additional icon informing the user about the sensor that is disconnected or is damaged will flash in the place of th...

Страница 15: ...its cables The user should also check if the controller is properly mounted and clean it if dusty or dirty Technical Data of ST 401N Controller Power Supply Voltage 230V 50Hz 10 Temperature Adjustment...

Страница 16: ...not replace the design of the CH installation It is aimed at demonstrating the possibility for expanding the controller The presented scheme of the heating installation does not contain cut off and pr...

Страница 17: ...Statistics 7 IV h 1 Gain 7 IV h 2 Collector Overheat 7 IV h 3 Power Supply Failures 7 IV i Backlight 7 IV j Display Contrast 7 IV k Language 7 IV l Information 7 IV m Factory Settings 8 V Service Men...

Страница 18: ...14 V h Alarm Sound 14 V i Factory Settings 14 V Protections 14 V Updating Software 15 VI Maintenance 15 VII Assembly 15 Care for the natural environment is our priority Being aware of the fact that w...

Страница 19: ...ctive LVD 2006 95 EC the Act dated April 13th 2007 on electromagnetic compatibility Journal of Laws 07 82 556 implementing the provisions of Directive EMC 2004 108 EC as well as the Regulation of the...

Страница 20: ...ST 401N User s Manual v 1 0 3 20...

Отзывы: