V. Updating Software 

 
       
NOTE 

New software may be uploaded to the controller only by a qualified fitter. After the software is changed, 
it is not possible to restore the previous settings.  
 
In order to upload new software, the controller should be disconnected from the power supply. A USB 
flash  drive  with  new  software  should  be  inserted  to  the  USB  port.  Then,  the  controller  should  be 
connected to the power supply while holding the MENU button all the time. The MENU button should 
be held until a single sound signal is heard – this means that the new software is being uploaded. 
 

VI. Maintenance 

Before and during the heating season, the ST-401N controller should be checked for the condition of 
its cables. The user should also check if the controller is properly mounted and clean it if dusty or dirty. 

Technical Data of ST-401N Controller

 

Power Supply Voltage 

230V/50Hz +/-10% 

Temperature Adjustment Range 

8°C:  90°C 

Power Consumption 

max.  4W 

Temperature Strength of PT 1000 Sensors  

-30°C: 200°C 

Measurement Accuracy 

1°C 

Ambient Temperature 

5°C:  50°C 

Load at Each Outlet 

1A 

Fuse Insert 

3,15A 

 
VII. Assembly 

 
NOTE: 

The device should be installed by a qualified electrician. Make sure that the plug is disconnected from 
the power supply at that time. 

 
CAUTION 

The cable to the temperature sensor should be led in a shield and should be protected against weather 
factors. The cable for connection to the solar controller should be permanent, made under a roof and 
well insulated. Metal elements of the sensor and the collector installation should be earthed.

 

 
Schematic Diagram of the Collector Installation 

Содержание ST-401N PWM

Страница 1: ...Tech 1 User s manual ST 401N PWM...

Страница 2: ...ure the regulator is disconnected from the mains before perform ing any activities involving the power supply plugging cables installing the device etc The device should be installed by a qualified el...

Страница 3: ...l signal relay is necessary to control the heater III Principle Of operation Description of the Control Panel of a Sample System Opis panelu steruj cego przyk adowego uk adu The regulator is controlle...

Страница 4: ...Active Operation Mode The Symbol of Active Additional Device Peripherals Automatic Operation Mode Circulation Pump Collector Defrosting Mode Firing up the Pellet Boiler voltage free signal Holiday Mo...

Страница 5: ...VICE MENU Pumps Solar Pump Deactivation Delta in this case the pump will be activated again when the temperature on the collector increases above the tank s temperature by the Solar Pump Activation De...

Страница 6: ...of activating the disinfection the temperature of disinfection needs to be reached in no longer than the time defined by the user SERVICE MENU Peripherals Heater Anti Legionella Maximum Anti Legionel...

Страница 7: ...ction of property IV h Statistics The parameters in this submenu allow the user to monitor the current conditions of the controller s operation IV h 1 Gain This parameter allows the user to monitor th...

Страница 8: ...essing the Menu button In order to return to the display s main view exit the service menu the user should use the Exit button by pressing it several times or waiting for approx 30 seconds the device...

Страница 9: ...m Reheating Temperature Alarm Hysteresis Defrosting Time Anti Freeze Temperature Collector Delta Pumps Regulated Revolutions Collector Maximum Temperature Solar Pump Deactivation Delta Solar Pump Acti...

Страница 10: ...oo hot in the container the Cooling Down to Set Value function should be started After activating this option when the collector s temperature drops below that of the container the pump is activated i...

Страница 11: ...ng the user declares the value of the collector s maximum alarm temperature when the pump may be damaged This temperature should be adjusted according to the collector s technical data Due to phenomen...

Страница 12: ...mpling aimed at updating the temperature reading consisting in a short activation of the collector s pump when normal conditions for the pump s activation are not met Sampling requires a short activat...

Страница 13: ...vate the heater Then the user selects the time interval in which the electric heating function will be active by means of the From and To functions V f 4 Contact not Consistent with Pump This setting...

Страница 14: ...vated and the following symbol will appear on the right hand side of the display An additional icon informing the user about the sensor that is disconnected or is damaged will flash in the place of th...

Страница 15: ...its cables The user should also check if the controller is properly mounted and clean it if dusty or dirty Technical Data of ST 401N Controller Power Supply Voltage 230V 50Hz 10 Temperature Adjustment...

Страница 16: ...not replace the design of the CH installation It is aimed at demonstrating the possibility for expanding the controller The presented scheme of the heating installation does not contain cut off and pr...

Страница 17: ...Statistics 7 IV h 1 Gain 7 IV h 2 Collector Overheat 7 IV h 3 Power Supply Failures 7 IV i Backlight 7 IV j Display Contrast 7 IV k Language 7 IV l Information 7 IV m Factory Settings 8 V Service Men...

Страница 18: ...14 V h Alarm Sound 14 V i Factory Settings 14 V Protections 14 V Updating Software 15 VI Maintenance 15 VII Assembly 15 Care for the natural environment is our priority Being aware of the fact that w...

Страница 19: ...ctive LVD 2006 95 EC the Act dated April 13th 2007 on electromagnetic compatibility Journal of Laws 07 82 556 implementing the provisions of Directive EMC 2004 108 EC as well as the Regulation of the...

Страница 20: ...ST 401N User s Manual v 1 0 3 20...

Отзывы: