ST-401N User's Manual v 1.0.3 

10

 - 

V.b) Accumulation Tank 

This menu allows the user to adjust all parameters related to the tank (heat container). 
 

V.b.1) Set Temperature 

This function is used to adjust the set temperature in the container which leads to the deactivation of 
the Collector Pump.   
 

V.b.2) Maximum Temperature of Tank 1 

Using this option, the user may declare the maximum acceptable safe temperature value to which the 
tank is allowed to heat in the case of Collector Overheat
 

If the collector reaches its alarm temperature (Overheat), the pump is activated automatically 

in order to cool down the heated collector, regardless of the set temperature. The pump operates until 
reaching the Tank's Maximum Temperature or until the collector's temperature drops by the value of 
the Alarm Hysteresis (see: SERVICE MENU > Solar Collector> Alarm Hysteresis
 

V.b.3) Minimum Temperature of Tank 1 

Using this parameter, the user may declare the minimum acceptable temperature value to which the 
tank is allowed to cool. Below this temperature, the pump does not activate in the Collector Defrosting 
mode. 

 

V.b.4) Tank Hysteresis 

Using this function, the user declares the tank hysteresis value. If the tank reaches the set temperature 
and the pump is deactivated, it will be activated again after the tank's temperature drops below the set 
value by the value of this hysteresis. 

 

V.b.5) Cooling Down to Set Value 

When the collector reaches the overheat temperature, the pump is activated in emergency mode to 
cool it down. In this case, the tank receives heating until exceeding the set temperature (up to the 
maximum temperature). To prevent the accumulation of water which is too hot in the container, the 
Cooling Down to Set Value function should be started. After activating this option, when the collector's 
temperature drops below that of the container, the pump is activated in order to cool down the tank 
until it reaches the set temperature. 
 

V.b.6) Delta Holiday 

This function is active only in the Holiday Operating mode. This parameter determines how many °C 
before reaching the collector overheat temperature the pump is activated in order to cool it down. The 
pump is deactivated after the collector's temperature is reduced by at least 5°C. 
 
 

IV.b) 

 

Solar Collector 

This menu allows the user to adjust all parameters related to the Solar Collector. 
 

V.c.1) Overheat Temperature 

This is the Solar Collector's acceptable alarm temperature at which the pump is forced to activate in 
order to cool down the solar panels.  The discharge of warm water will take place regardless of the 
tank's set temperature. The pump will operate until its temperature drops below the alarm temperature 
by the Alarm Hysteresis Value (Service Settings > Solar Collector > Alarm Hysteresis) or until the tank 
reaches  the  maximum  acceptable  temperature  (Service  Settings  >  Accumulation  Tank  >  Maximum 
Temperature

 

V.c.2) Minimum Reheating Temperature 

This is the collector's threshold temperature. If the temperature within the collector is higher and is 
dropping after reaching the minimum reheating temperature, the pump is deactivated. On the other 
hand, when the temperature on the collector is below this limit and is increasing - the pump is activated 
after  reaching  the  minimum  reheating  temperature  plus  hysteresis  -  3°C.  The  threshold  reheating 
temperature is not active in the emergency mode, manual operation or collector defrosting. 

 

V.c.3) Anti-Freeze Temperature 

Due  to  the  different  freezing  temperatures  of  the  liquid  in  the  solar  installation,  the  Anti-Freeze 

Содержание ST-401N PWM

Страница 1: ...Tech 1 User s manual ST 401N PWM...

Страница 2: ...ure the regulator is disconnected from the mains before perform ing any activities involving the power supply plugging cables installing the device etc The device should be installed by a qualified el...

Страница 3: ...l signal relay is necessary to control the heater III Principle Of operation Description of the Control Panel of a Sample System Opis panelu steruj cego przyk adowego uk adu The regulator is controlle...

Страница 4: ...Active Operation Mode The Symbol of Active Additional Device Peripherals Automatic Operation Mode Circulation Pump Collector Defrosting Mode Firing up the Pellet Boiler voltage free signal Holiday Mo...

Страница 5: ...VICE MENU Pumps Solar Pump Deactivation Delta in this case the pump will be activated again when the temperature on the collector increases above the tank s temperature by the Solar Pump Activation De...

Страница 6: ...of activating the disinfection the temperature of disinfection needs to be reached in no longer than the time defined by the user SERVICE MENU Peripherals Heater Anti Legionella Maximum Anti Legionel...

Страница 7: ...ction of property IV h Statistics The parameters in this submenu allow the user to monitor the current conditions of the controller s operation IV h 1 Gain This parameter allows the user to monitor th...

Страница 8: ...essing the Menu button In order to return to the display s main view exit the service menu the user should use the Exit button by pressing it several times or waiting for approx 30 seconds the device...

Страница 9: ...m Reheating Temperature Alarm Hysteresis Defrosting Time Anti Freeze Temperature Collector Delta Pumps Regulated Revolutions Collector Maximum Temperature Solar Pump Deactivation Delta Solar Pump Acti...

Страница 10: ...oo hot in the container the Cooling Down to Set Value function should be started After activating this option when the collector s temperature drops below that of the container the pump is activated i...

Страница 11: ...ng the user declares the value of the collector s maximum alarm temperature when the pump may be damaged This temperature should be adjusted according to the collector s technical data Due to phenomen...

Страница 12: ...mpling aimed at updating the temperature reading consisting in a short activation of the collector s pump when normal conditions for the pump s activation are not met Sampling requires a short activat...

Страница 13: ...vate the heater Then the user selects the time interval in which the electric heating function will be active by means of the From and To functions V f 4 Contact not Consistent with Pump This setting...

Страница 14: ...vated and the following symbol will appear on the right hand side of the display An additional icon informing the user about the sensor that is disconnected or is damaged will flash in the place of th...

Страница 15: ...its cables The user should also check if the controller is properly mounted and clean it if dusty or dirty Technical Data of ST 401N Controller Power Supply Voltage 230V 50Hz 10 Temperature Adjustment...

Страница 16: ...not replace the design of the CH installation It is aimed at demonstrating the possibility for expanding the controller The presented scheme of the heating installation does not contain cut off and pr...

Страница 17: ...Statistics 7 IV h 1 Gain 7 IV h 2 Collector Overheat 7 IV h 3 Power Supply Failures 7 IV i Backlight 7 IV j Display Contrast 7 IV k Language 7 IV l Information 7 IV m Factory Settings 8 V Service Men...

Страница 18: ...14 V h Alarm Sound 14 V i Factory Settings 14 V Protections 14 V Updating Software 15 VI Maintenance 15 VII Assembly 15 Care for the natural environment is our priority Being aware of the fact that w...

Страница 19: ...ctive LVD 2006 95 EC the Act dated April 13th 2007 on electromagnetic compatibility Journal of Laws 07 82 556 implementing the provisions of Directive EMC 2004 108 EC as well as the Regulation of the...

Страница 20: ...ST 401N User s Manual v 1 0 3 20...

Отзывы: