50
5 Press the
button to start the battery test.
During the battery test, the UPS transfers to Battery mode and
discharges the batteries for 25% of the original expected runtime.
The status screen displays “Battery test running” and the percentage
of the test completed. The results display on the UPS status screen
as completing.
6.5 Recycling the Used Battery or UPS
Contact your local recycling or hazardous waste center for
information on proper disposal of the used battery or UPS.
51
7. Specifications
This chapter provides the following specifications:
l
Model list
l
General Specification
l
Electrical Performance
l
Environmental and Safety
7.1 Electrical specification
Model
Online RT 6K
Online RT 10K
Output
Power Capacity
6KVA/5.4KW
10KVA/9KW
Voltage Range
208VAC/220VAC/
230VAC/ 240VAC
208VAC/220VAC/
230VAC/ 240VAC
Frequency
50/60Hz
50/60Hz
Voltage Distortion
<5%@Nonlinear load
<2%@Linear load
<5%@Nonlinear load
<2%@Linear load
Over Load
Line Mode:
2mins 102% ~ 130%
30s 130% ~ 150%
100ms >150%
Battery Mode:
10s 102% ~ 130%
100ms >130%
Efficiency
Line mode
>92%
>93%
ECO mode
>96%
>97%
Battery mode
>89%
>90%
Input
Input wire
1 Ph (L1,L2/N)+ PE
Input Type
Support dual input
Phase
Single
Voltage Range
176-276Vac
Frequency Range
(45~55)/(54~66)Hz