36 

software (Winpower, etc.). 

2)  It is attention that the transfer time 

of  UPS  output  from  HE  mode  to 

battery mode is about 10ms. But it 

is  still  too  long  for  some  sensitive 

load. 

Fig 5-8 

Converter mode 

In converter mode, the UPS would free 

run  with  fixed  output  frequency  (50Hz 

or  60Hz).  Once  the  mains  is  loss  or 

abnormal,  the  UPS  would  transfer  to 

battery mode  and  the  load  is  supplied 

continuously. 

1)  The  function  could  be  enabled 

through  the  LCD  setting  or  the 

software (Winpower, etc.). 

2)  The  load  have  to  be  derated  to 

80% in converter mode. 

Fig 5-9 

Warning: 

When the warning occurs, it illustrates 

that 

there 

are 

some 

abnormal 

problems during the operation of UPS. 

Normally  the  problems  are  not  fatal 

and  the  UPS  continues  working,  but 

they should be paid attention to, or the 

UPS may fail. 

Fig 5-10 

Fault: 

When the fault occurs, it illustrates that 

some  fatal  problems  happened,  the 

UPS would directly cut off the output or 

transfer to bypass, and keep alarming. 

The  backlight  of  LCD  would  also  turn 

to red.   

37 

Fig 5-11 

Overload: 

When  the  UPS  is  overload,  the  alarm 

will  beep  twice  every  second.  Some 

unnecessary loads should be get rid of 

one  by  one  to  decrease  the  loads 

connected to the UPS. 

 

Fig 5-12 

Battery Test 

UPS is executing a battery test

 

Fig 5-13 

Battery fail: 

if the battery status detected is “bad 

battery detected” or “battery 

disconnected”, the symbol of battery 

failure would be shown and UPS would 

alarm. 

 

5.3 Turning on and Turning off UPS   

Attention: 

The UPS could only be turning on while connecting with the 

utility for the first time. 

Attention:

 Please switch off the connected loads at first before turning 

on the UPS, and switch on the loads one by one after the UPS is turned 

on. Switch off all of the connected loads before turning off the UPS. 

5.3.1 Turning on UPS with utility 

1)  Check all the connection is correct.   

2)  Power on the UPS, the fan begins to rotate, LCD will switch-ON. 

After that, the LCD will show the default UPS status summary 

screen. 

3)  Pressing 

  button  continuously  for  more  than  1  second,  the 

buzzer will beep 1s, UPS starts to turn on. 

Содержание AP160N-10K

Страница 1: ...tup 19 3 7 Installation of UPS with AC inputs 20 4 Power cables connection Startup 22 4 1 Access to terminal block 23 4 2 Common input sources connection 23 4 3 Separate input sources connection 24 4...

Страница 2: ...wer problems such as power failures power sags power surges brownout and line noise Power outages can occur when you least expect them and power quality can be erratic These power problems have the po...

Страница 3: ...timize recharge time l Selectable High Efficiency mode Eco Mode of operation l Start on battery capability for powering up the UPS even if utility power is not available l Standard communication optio...

Страница 4: ...fety instructions and important regulatory information in your Safety Environmental and Regulatory Information document 5 neutral conductor have to be provided in the building wiring installation l Th...

Страница 5: ...high short circuit current and pose a risk of shock Take all precautionary measures specified as below and any other measures necessary when working with batteries 1 Remove all jewellery wristwatches...

Страница 6: ...ns and packing materials for the carrier or place of purchase and file a claim for shipping damage If you discover damage after acceptance file a claim for concealed damage Note Check the battery rech...

Страница 7: ...on on each side carefully lift the cabinet out of the outer carton using the handles on the cardboard and set it on a flat stable surface see Figure 3 3 3 4 Place the cabinet in a protected area that...

Страница 8: ...it for future use 3 3 UPS Rear Panel This section shows the rear panel of the Online R T models 6K model Figure 3 5A 6K Rear Panel single parallel without maintenance bypass 13 Figure 3 5B 6K PDU Rea...

Страница 9: ...binets into the rack requires a minimum of two people CAUTION Removing the batteries requiered precautions which should be performed or supervised by personnel with knowledge of batteries Keep unautho...

Страница 10: ...g rails in the rack then install the UPS in the sliding rail 17 Figure 3 12 Install the sliding rails 7 For 10K Install the battery pack and battery protection plate then fix the front panel Figure 3...

Страница 11: ...2 Replace UPS s front panel and EBM s front panel Figure 3 15 Replace UPS s front panel and EBM s front panel 19 10K Model Figure 3 16 Plug the EBM cable into the UPS battery connector 3 6 Tower Setu...

Страница 12: ...systems are identical Otherwise a transformer is necessary UPS with common Normal and Bypass AC inputs UPS with separate Normal and Bypass AC inputs Earthing systems are identical Earthing systems are...

Страница 13: ...ery Cabinet Positive Pole Negative pole Min conductor cross section 4mm 2 10AWG 10mm2 6AWG External Battery Cabinet Fuse in Positive Pole Negative pole 60A 80A The UPS does not have an automatic prote...

Страница 14: ...do not exceed the UPS capacity to prevent an overload alarm 1 Verify that the internal batterties are connected 2 If optional EBMs are installed verify that the EBMs are connected to the UPS 3 Set th...

Страница 15: ...on the UPS display Deactivate the external REPO switch and restart the UPS 4 6 Parallel Installation and Operation 4 6 1 Brief introduction of the redundancy The parallel structure is 1 1 As long as...

Страница 16: ...28 Figure 4 5 a Parallel systerm wiring diagram of 6K 10K 29 Figure 4 5 b Parallel System Installation Diagram...

Страница 17: ...press the button to turn off the UPS then UPS will work in bypass mode 31 4 Set the main maintenance bypass switch from UPS to ByPass then switch off the main output breaker and the input breaker and...

Страница 18: ...in menu Press this button for 1s to exit the present menu to default system status display menu without executing a command or changing a setting Scroll up Press this button for 0 1sec 1s to scroll up...

Страница 19: ...operating mode or status 35 Table 5 3 Status Summary Screens Status Summary Screen Description Fig 5 3 Normal mode The UPS is operating in Normal mode from utility power Fig 5 4 Battery mode When the...

Страница 20: ...bypass and keep alarming The backlight of LCD would also turn to red 37 Fig 5 11 Overload When the UPS is overload the alarm will beep twice every second Some unnecessary loads should be get rid of on...

Страница 21: ...order to cut off the UPS output simply cut off the utility power supply A few seconds later LCD display shuts down and no output voltage is available from the UPS output terminal 5 3 4 Turning off UP...

Страница 22: ...atus please see Fig5 14 5 4 3 The event log menu By pressing on the menu of Event log the display would enter the next event menu tree All the previous events alarm and fault have been recorded here T...

Страница 23: ...menu tree 5 4 5 The control menu By pressing on the menu of Control the display would enter the next control menu tree 1 Start Battery Test this is one command that control the UPS to do the battery...

Страница 24: ...press on the menu of Identification the display would enter the next identification menu tree The identification information includes UPS serial number firmware serial number model type would be show...

Страница 25: ...unction loss even directly damage the load battery or UPS Most of settings could only be done while UPS is in Bypass mode Figure 5 19 Setting menu tree 47 Example set rated output voltage value Figure...

Страница 26: ...disconnected from utility power 2 Place the UPS on a flat stable surface with the front of the cabinet facing you 49 3 Remove the UPS front cover 4 Disconnect the internal battery connectors 5 Fix the...

Страница 27: ...chapter provides the following specifications l Model list l General Specification l Electrical Performance l Environmental and Safety 7 1 Electrical specification Model Online RT 6K Online RT 10K Ou...

Страница 28: ...y are preventive alarms intended to alert the user Active alarms are accompanied by an audible buzzer The control panel provides troubleshooting information from two main menus l UPS status menu Acces...

Страница 29: ...s replaced Contact your service representative 55 Output Overload Alarm Code 41 Output is overload Remove some of the equipment from the UPS The UPS continues to operate but may switch to Bypass mode...

Страница 30: ...e charger until the next power recycle Contact your service representative Battery Over Voltage Alarm Code 16 Indicates that the battery voltage is too high The UPS will turn off the charger until the...

Страница 31: ...itiates the saving of all data and an orderly shutdown of the equipment The cable pins for the RS 232 communication port are identified in figure 9 1 and the pin functions are described in Table 3 Fig...

Страница 32: ...your UPS This unique software provides safely auto shutdown for multi computer systems while power failure With this software users can monitor and control any UPS on the same LAN no matter how far fr...

Страница 33: ...62 614 08108 00...

Отзывы: