background image

26 

8.  If  optional  EBMs  are  installed,  see  “Configuring  the  UPS  for 

EBMs” to set the number of installed EBMs. 

9.  To change any other factory-set defaults, see “Operation” 

Online series recommends setting the date and time. 

At  initial  startup,  the  UPS  sets  system  frequency  according  to 
input line frequency (input frequency auto-sensing is enabled by 
default).  After  initial  startup,  auto-sensing  is  disabled  until 
manually re-enabled by output frequency setting. 

At initial startup, inut voltage auto-sensing is disbaled by default. 
When manually enabled by output voltage setting, at the next AC 
startup  the  UPS  sets  output  voltage  according  to  input  line 
voltage.  After  the  subsequent  startup,  auto-sensing  is  disabled 
until manually re-enabled by output voltage setting. 

10. If you installed an optional REPO, test the REPO function: 

Activate the external REPO switch. Verify that status change on 
the UPS display. 

Deactivate the external REPO switch and restart the UPS. 

4.6 Parallel Installation and Operation

 

     

4.6.1 Brief introduction of the redundancy 

The parallel  structure  is 1+1.As  long  as  the UPS  is  equipped  with 

parallel  cables,  up  to  2  UPSs  can  be  connected  in  parallel  to 

configure a sharing and redundant output power.   

 

4.6.2 Installation and operation 

How to install a new parallel UPS system:

 

1)  Before  installing  a  new  parallel  UPS  system,  user  need  to 

prepare  the  input  and  output  wires,  the  input  and  output 

breakers, and the parallel signal cables.   

2)  Users  need  to  use  a  special  15-pins  communication  cable 

(optional)  for  this  system,  which  have  to  have  15  cores, 

corresponding  stitches  and  shield,  as  the  UPS  parallel  cable. 

27 

The length of the parallel cable have to be less than 3 m. 

3)  Strictly  follow  the  chapter  4,  the  wiring  requirement  of  single 

UPS to perform the wiring of each UPS.   

4)  Each UPS need independent battery packs. 

5)  Please  connect  the  input  and  output  wires,  fix  all  the  wiring 

according to the Figure 4-5 and make sure all these breakers 

are open. 

 
 
 
 
 
 

Содержание AP160N-10K

Страница 1: ...tup 19 3 7 Installation of UPS with AC inputs 20 4 Power cables connection Startup 22 4 1 Access to terminal block 23 4 2 Common input sources connection 23 4 3 Separate input sources connection 24 4...

Страница 2: ...wer problems such as power failures power sags power surges brownout and line noise Power outages can occur when you least expect them and power quality can be erratic These power problems have the po...

Страница 3: ...timize recharge time l Selectable High Efficiency mode Eco Mode of operation l Start on battery capability for powering up the UPS even if utility power is not available l Standard communication optio...

Страница 4: ...fety instructions and important regulatory information in your Safety Environmental and Regulatory Information document 5 neutral conductor have to be provided in the building wiring installation l Th...

Страница 5: ...high short circuit current and pose a risk of shock Take all precautionary measures specified as below and any other measures necessary when working with batteries 1 Remove all jewellery wristwatches...

Страница 6: ...ns and packing materials for the carrier or place of purchase and file a claim for shipping damage If you discover damage after acceptance file a claim for concealed damage Note Check the battery rech...

Страница 7: ...on on each side carefully lift the cabinet out of the outer carton using the handles on the cardboard and set it on a flat stable surface see Figure 3 3 3 4 Place the cabinet in a protected area that...

Страница 8: ...it for future use 3 3 UPS Rear Panel This section shows the rear panel of the Online R T models 6K model Figure 3 5A 6K Rear Panel single parallel without maintenance bypass 13 Figure 3 5B 6K PDU Rea...

Страница 9: ...binets into the rack requires a minimum of two people CAUTION Removing the batteries requiered precautions which should be performed or supervised by personnel with knowledge of batteries Keep unautho...

Страница 10: ...g rails in the rack then install the UPS in the sliding rail 17 Figure 3 12 Install the sliding rails 7 For 10K Install the battery pack and battery protection plate then fix the front panel Figure 3...

Страница 11: ...2 Replace UPS s front panel and EBM s front panel Figure 3 15 Replace UPS s front panel and EBM s front panel 19 10K Model Figure 3 16 Plug the EBM cable into the UPS battery connector 3 6 Tower Setu...

Страница 12: ...systems are identical Otherwise a transformer is necessary UPS with common Normal and Bypass AC inputs UPS with separate Normal and Bypass AC inputs Earthing systems are identical Earthing systems are...

Страница 13: ...ery Cabinet Positive Pole Negative pole Min conductor cross section 4mm 2 10AWG 10mm2 6AWG External Battery Cabinet Fuse in Positive Pole Negative pole 60A 80A The UPS does not have an automatic prote...

Страница 14: ...do not exceed the UPS capacity to prevent an overload alarm 1 Verify that the internal batterties are connected 2 If optional EBMs are installed verify that the EBMs are connected to the UPS 3 Set th...

Страница 15: ...on the UPS display Deactivate the external REPO switch and restart the UPS 4 6 Parallel Installation and Operation 4 6 1 Brief introduction of the redundancy The parallel structure is 1 1 As long as...

Страница 16: ...28 Figure 4 5 a Parallel systerm wiring diagram of 6K 10K 29 Figure 4 5 b Parallel System Installation Diagram...

Страница 17: ...press the button to turn off the UPS then UPS will work in bypass mode 31 4 Set the main maintenance bypass switch from UPS to ByPass then switch off the main output breaker and the input breaker and...

Страница 18: ...in menu Press this button for 1s to exit the present menu to default system status display menu without executing a command or changing a setting Scroll up Press this button for 0 1sec 1s to scroll up...

Страница 19: ...operating mode or status 35 Table 5 3 Status Summary Screens Status Summary Screen Description Fig 5 3 Normal mode The UPS is operating in Normal mode from utility power Fig 5 4 Battery mode When the...

Страница 20: ...bypass and keep alarming The backlight of LCD would also turn to red 37 Fig 5 11 Overload When the UPS is overload the alarm will beep twice every second Some unnecessary loads should be get rid of on...

Страница 21: ...order to cut off the UPS output simply cut off the utility power supply A few seconds later LCD display shuts down and no output voltage is available from the UPS output terminal 5 3 4 Turning off UP...

Страница 22: ...atus please see Fig5 14 5 4 3 The event log menu By pressing on the menu of Event log the display would enter the next event menu tree All the previous events alarm and fault have been recorded here T...

Страница 23: ...menu tree 5 4 5 The control menu By pressing on the menu of Control the display would enter the next control menu tree 1 Start Battery Test this is one command that control the UPS to do the battery...

Страница 24: ...press on the menu of Identification the display would enter the next identification menu tree The identification information includes UPS serial number firmware serial number model type would be show...

Страница 25: ...unction loss even directly damage the load battery or UPS Most of settings could only be done while UPS is in Bypass mode Figure 5 19 Setting menu tree 47 Example set rated output voltage value Figure...

Страница 26: ...disconnected from utility power 2 Place the UPS on a flat stable surface with the front of the cabinet facing you 49 3 Remove the UPS front cover 4 Disconnect the internal battery connectors 5 Fix the...

Страница 27: ...chapter provides the following specifications l Model list l General Specification l Electrical Performance l Environmental and Safety 7 1 Electrical specification Model Online RT 6K Online RT 10K Ou...

Страница 28: ...y are preventive alarms intended to alert the user Active alarms are accompanied by an audible buzzer The control panel provides troubleshooting information from two main menus l UPS status menu Acces...

Страница 29: ...s replaced Contact your service representative 55 Output Overload Alarm Code 41 Output is overload Remove some of the equipment from the UPS The UPS continues to operate but may switch to Bypass mode...

Страница 30: ...e charger until the next power recycle Contact your service representative Battery Over Voltage Alarm Code 16 Indicates that the battery voltage is too high The UPS will turn off the charger until the...

Страница 31: ...itiates the saving of all data and an orderly shutdown of the equipment The cable pins for the RS 232 communication port are identified in figure 9 1 and the pin functions are described in Table 3 Fig...

Страница 32: ...your UPS This unique software provides safely auto shutdown for multi computer systems while power failure With this software users can monitor and control any UPS on the same LAN no matter how far fr...

Страница 33: ...62 614 08108 00...

Отзывы: