83-530-000 Rev. G
55
1
IDN?
Returns the power supply model identification as an ASCII string:
TDK-Lambda
,
GENX-Y
2
REV?
Returns the software version as an ASCII string.
3
SN?
Returns the unit serial number. Up to 12 characters.
4
DATE?
Returns date of last test. Date format: yyyy/mm/dd
7.7.5
Output control commands
#
Command
Description
1
PV n
Sets the output voltage value in Volts. The range of voltage value is described in
Table 7-3. The maximum number of characters is 12. See the following examples
for PV n format: PV 12, PV 012, PV 12.0, PV 012.00, etc…
2
PV?
Reads the output voltage setting. Returns the string “n” where “n” is the exact string
sent in the PV n command. When in Local mode, returns the PREVIEW (front
panel) settings in a 5 digits string.
3
MV?
Reads the actual output voltage. Return 5 digits string.
Example: 60V supply sends 01.150, 15.012, 50.000, etc…
4
PC n
Set the output current value in Amperes. The range of current values is described
in Tables 7-4 and 7-5. The maximum number of characters is 12. See the following
examples for PC n format: PC n format: PC 10, PC 10.0, PC 010.00, etc…
5
PC?
Reads the output current setting. Returns the string “n” where “n” is the exact string
sent in the PC n command. When in Local mode, returns the PREVIEW (front
panel) settings in a 5 digits string.
6
MC?
Reads the actual output current. Returns 5 digits string.
Example: 200A supply sends 000.50, 110.12, 200.00, etc…
7.7.5
Output control commands-cont.
7
DVC?
Display Voltage and Current data. Data will be returned as a string of ASCII charac-
ters. A comma will separate the different fields. The fields, in order, are: Measured
Voltage, Programmed Voltage, Measured Current, Programmed Current, Over Volt-
age Set Point and Under Voltage Set Point.
Example: 5.9999,6.0000,010.02,010.00,7.500,0.000
8
FILTER nn
Set the low pass filter frequency of the A to D Converter for Voltage and Current
Measurement where nn = 18, 23 or 46.
9
FILTER?
Returns the A to D Converter filter frequency: 18,23 or 46 Hz.
10
OUT n
Turns the output to ON or OFF. Recover from Safe-Start, OVP or FLD fault.
OUT 1 (or OUT ON)-Turn On.
OUT 0 (or OUT OFF)-Turn Off
11
OUT?
Returns the output On/Off status string.
ON - output On.
OFF - output Off.
12
FLD n
Sets the Foldback protection to ON or OFF.
FLD 1 (or FOLD ON) - Arms the Foldback protection
FLD 0 (or FOLD OFF) - Cancels the Foldback protection.
When the Foldback protection has been activated, OUT 1 command will release the
protection and re-arm it, while FLD 0 will cancel the protection.
13
FLD?
Returns the Foldback protection status string:
“ON” - Foldback is armed.
“OFF” - Foldback is cancelled.
14
FBD nn
Add (nn x 0.1) seconds to the Fold Back Delay. This delay is in addition to the stan-
dard delay. The range of nn is 0 to 255. The value is stored in eprom at AC power
down and recovered at AC power up.
15
FBD ?
Supply returns the value of the added Fold Back Delay.
16
FBDRST
Reset the added Fold Back Delay to zero.