18
5.
For load wires with a diameter greater than 11 millimeter divide each bus bar cover plug into two separate
parts by bending and breaking it along its separate grooves, as illustrated in Figure 20. Insert only the
rounded parts into the bus bar protection bracket and fix it to the output cover using two SEMS screw.
Insert output cover assembly through the cables as illustrated in Figure 20.
Figure 20: Two 60V÷100V Units, Wire Diameter
>
11mm, Output Cover Assembly
6.
Assemble one lug on each bus bar using one hexagon bolt, two plain washers, one helical spring-lock
washer and one hexagon nut as illustrated in Figure 21.
Figure 21: Two 60V÷100V Units Lugs Assembly
Separate Grooves
Bus Bar Protection Bracket
Bus Bar Cover Plug
M3 x 8 SEMS Screw, Nickel Plated
Tightening torque: 4.7-5.7 Lbf-inch (0.53-0.64Nm)
Output Cover
Output Cover Assembly
For recommended lugs refer
to
series Safety &
Installation Manual.
Not supplied.
Hexagon Nut, M8, Stainless Steel
Helical Spring-Lock Washer, M8, Stainless Steel
Plain Washer, M8, Stainless Steel
M8 x 25 Hexagon Bolt, Stainless Steel
Tightening torque: 106-132 Lbf-inch (12-14.9 Nm)