20
1.4.4.2
Installation Steps
1.
Attach connection plates, one on each side of the power supplies, using eight pan head screws, eight helical
spring-lock washers and eight plain washers as illustrated in Figure 23.
Figure 23: Two
150V÷600V Units Connection Plates 2U Assembly
2.
Connect paralleling cable from top unit M connector to bottom unit S connector as illustrated in Figure 24.
Figure 24: Two 150V÷600V Units Paralleling Cable Connection
Connection Plate 2U
Plain Washer, No. 10, Stainless Steel
Helical Spring-Lock Washer, No. 10, Stainless Steel
10-32 x 5/16 Pan Head Screw, Stainless Steel
Tightening torque: 25.4-31.7 Lbf-inch (2.87-3.58Nm).
Paralleling Cable