background image

2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

7

the room occupied, such as with a switch or wind-up 

timer. If each occupancy period is about the same, (the-

aters, meetings) another option is to set the DI3 to exter-

nal time clock, and use the timed override button to put 

the unit in occupied mode.
To make the unit always occupied, set DI3 to external 

time clock and short the DI3 terminal to ground.

TWO-PIPE FAN COIL OPERATION

For two-pipe fan coil operation, in step #31 select YES. 

You must then select whether the system is HEATing 

only, COOLing only or heating and cooling (H&C) in step 

#32.
When using a two-pipe system to do both heating and 

cooling, the SZ1061 and SZ1062 need to know whether 

hot or cold water is available. This is accomplished by 

either the use of a mechanical aquastat (bulb thermo-

stat) connected to terminals DI1 and 24-, or by the use 

of a temperature sensor connected to T2 and T2 

(SZ1062 only). If using a mechanical thermostat, select 

DIGITAL in step #33, and select normally closed N.C. or 

normally open N.O. In step #34. If using a temperature 

sensor, select ANALOG in step #33 and place a change-

over setpoint in step #35. When the temperature is 

greater than this setpoint, it is assumed hot water is 

available and heating is done. When the temperature is 

less than this setpoint, it is assumed cold water is avail-

able and cooling is done.
When using a two-pipe system to do both heating and 

cooling, only Y1 is used. When using a two-pipe system 

to do only heating, only W1 is used. When using a two-

pipe system to do only cooling, only Y1 is used.

FOUR-PIPE FAN COIL OPERATION

For four-pipe fan coil operation, in step #31 select NO. 
Four-pipe fan coil operation assumes that there are two 

water sources available (hot and cold), that are each 

controlled by its own valve. W1 output one is used for 

heating and Y1 is used for cooling.

PIPE TEMPERATURE SENSING

The SZ1062 accepts a remote pipe temperature sensor 

for monitoring purposes or for changeover in a two-pipe 

system.  (See setup instructions for dipswitch placement 

for this option.)
The pipe temperature span is 0 to 150°F (-17.8 to 

65.6°C).

DIGITAL OUTPUTS

The digital outputs on the SZ1061 and SZ1062 are used 

to control the heating and cooling in a space. Digital out-

put W1 is used to control heating and digital Y1 is used 

to control cooling with a four pipe system. Only digital Y1 

is used with a two-pipe system set for heat and cool 

(H&C).

DI2 SETPOINT SHIFT

The SZ1061 and SZ1062 allow DI2 to be set for setpoint 

shift for energy demand setback. A digital contact that 

closes when setback is needed should be wired into DI2. 

You may specify a number of degrees such that, when 

the thermostat is operating in the occupied mode, and 

DI2 is closed, the heating setpoint will be lowered this 

number of degrees, and the cooling setpoint will be 

raised this number of degrees. The fan will continue to 

operate according to its occupied setting. If you are 

using DI2 as monitor for another purpose, make sure to 

set the setpoint shift value to zero.

AUXILIARY RELAY OUTPUT PARAMETERS

The auxiliary relay of the SZ1062 will control one stage 

of either heating or cooling, or can be used as a time-

clock output.
If the auxiliary relay is used as heating or cooling stage, 

you may specify an offset and a differential value. The 

offset value is the amount away from the setpoint a 

stage will turn off. By assigning a value other than zero, 

you "anticipate" that the residual heat or cooling in the 

duct will bring the temperature back to setpoint. In most 

cases, a first stage is set to zero. The differential value 

is the difference between the on and off points. Using an 

offset value greater than or equal to the differential of a 

heat or cooling output will allow the relay to come on 

after first stage is achieved. Strip heat, for example.
If the auxiliary relay is used as a timeclock output, it is 

selectable whether the relay is open or closed during the 

occupied period. During the unoccupied period, the 

opposite will occur.
Keep in mind that although it is an isolated relay (sepa-

rate common terminal), it is rated at 24 VAC @ 2A. For 

loads that exceed this, use an external relay. The follow-

ing chart shows operation of W1, Y1 and auxiliary relay.

Содержание SZ1061

Страница 1: ...Z1062 only Adjustable delay on start up and power up for soft starts Smart recovery SZ1062 only Local and remote override capability External time clock and override options Auxiliary output for heat...

Страница 2: ...using a single transformer the polarity of the power wiring must be maintained because all TCS devices are half wave rectified and have common return paths When the Superstat is used as a stand alone...

Страница 3: ...through the PC consult your TCS software manual PROGRAMMING THROUGH THE KEYPAD To access the programming screens press the program setup button Screens A thru F are monitoring screens and programming...

Страница 4: ...to two occupied periods SZ1062 only Schedule Announcement Screen Announces the next screen SZ1062 only Copy Schedule Screen Choose to use the same schedule that was used for the previous day If so the...

Страница 5: ...tput a stage of HEAT or a stage of COOL SZ1062 only Time Clock Output Screen Choose whether the auxiliary output will be OPEN or CLOSED during occupied periods This screen is not used if step 29 is se...

Страница 6: ...ime remaining elapses they may press the override button again Additionally an Override Hold feature is built into the thermostats When in unoccupied mode pressing the override once and then pressing...

Страница 7: ...em See setup instructions for dipswitch placement for this option The pipe temperature span is 0 to 150 F 17 8 to 65 6 C DIGITAL OUTPUTS The digital outputs on the SZ1061 and SZ1062 are used to contro...

Страница 8: ...NOTE The fan has a minimum on and off time of 30 seconds A relay for heating or cooling has a minimum on and off time of 2 minutes NOTE The SZ1061 does not show the day or time 2 Turn power on The th...

Страница 9: ...If any of the temperatures are still reading slightly high or low you can add in a temperature offset calibration using Ubiquity or TCS Insight In Ubiquity you can edit the calibration off set for eac...

Страница 10: ...80 minutes This value may be changed from 0 to 255 minutes in programming step 23 SETTING CLOCK SCHEDULE The ability to set the clock and schedule is allowed by factory default An access code may be r...

Отзывы: