TCS Basys Controls SZ1061 Скачать руководство пользователя страница 9

2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

9

9. Go back to programming step #22 and set the set-

point adjust limit back to the desired value. Make any 

other changes in programming, clock, and schedule. Set 

the fan and system modes to their desired settings. 
10. If using remote sensor(s), verify that the reading is 

correct. If not, see Wrong Temperature Display in 

Troubleshooting section.

TROUBLESHOOTING
No Display

Check for 24 VAC on terminals "+24" and "-24". Check 

the cable connecting the cover to the base for a good 

connection.

Fan Does Not Come On 

The fan is on whenever the fan LED is on. If the fan 

should be on, but the fan LED is off, check the occupied 

and unoccupied fan mode in programming. If the Fan 

Status is OFF, press the Low, Medium or High button. If 

the fan is off but the fan LED is on, check wiring. Short 

terminals "R" to "GL", "GM" or "GH" and see if the fan 

comes on. This is a check for a mechanical relay failure.

Heating or Cooling Does Not Come On

Heating is on whenever the  heating LED is on, and 

cooling is on whenever the cooling LED is on. If heating 

or cooling should be on but the heating or cooling LED 

is off, check the fan and system modes. Also, check the 

heating and cooling setpoints, offsets and differentials, 

and the room temperature to be sure heating or cooling 

should be on. 

Wrong Temperature Display

Initially, verify the wiring connections to check for problems 

(poor connections, opens, or shorts). If the temperature is 

at a minimum or maximum reading, check that the sensor 

dipswitch positions are correct as shown in the Setup sec-

tion of this document. Also, verify the resistance reading for 

the sensor in question. A remote sensor should read 1080 

to 1090 ohms at room temperature. The built-in sensor 

should read 108 to 109 ohms at room temperature. If any 

of the temperatures are still reading slightly high or low, you 

can add in a temperature offset (calibration) using Ubiquity 

or TCS Insight. In Ubiquity, you can edit the calibration off-

set for each temperature input (room, discharge, outdoor 

air, etc.) on the controller's programming page. For exam-

ple, if the room temperature is reading 2 degrees high, you 

would subtract 2 from the existing offset in the room tem-

perature calibration offset field and submit the page. In TCS 

Insight, the process is similar. Refer to the Calibrate Using 

TCS Insight Tech Bulletin # 1019 for details. As a last resort 

and only when directed to do so by TCS technical support, 

you may be able to use the on-board adjustment pots. 

Refer to the Thermostat Sensor Calibration Tech Bulletin # 

1005 for details.

Outputs Will Not Shut Off

First check the room temperature and the setpoints and 

determine whether the output should be on. There are 

delays and minimum on and off times for the fan and 

heating and cooling stages. Also, check the service 

menus to verify that the outputs are on. Turning the sys-

tem to "off" will instantly turn all outputs off. The thermo-

stat can be reset by pressing the system switch button 

and the service status button simultaneously.

Output Operation is not Correct

Check programmed parameters, in particular "Offset"and 

"Differential" selections and "Delay Times" for the relay 

outputs. Check wiring.

LED Description                       

Six LEDs on the face allow the occupant to view the cur-

rent operating status of the thermostat.

OCCUPIED

This LED will be lit whenever the unit is operating in the 

occupied mode.

HEATING

This LED will be lit when any heat output is operating.

COOLING

This LED will be lit when any cool output is operating. 

DATA / PROGRAM

This LED will be lit when the thermostat is within the pro-

gramming or clock setup menus. It will blink when the 

unit is being accessed by a PC.

SERVICE

This LED will be lit when DI2 is closed.

FAN

This LED will be lit when the fan output is closed.

Limiting Occupant Access         

Содержание SZ1061

Страница 1: ...Z1062 only Adjustable delay on start up and power up for soft starts Smart recovery SZ1062 only Local and remote override capability External time clock and override options Auxiliary output for heat...

Страница 2: ...using a single transformer the polarity of the power wiring must be maintained because all TCS devices are half wave rectified and have common return paths When the Superstat is used as a stand alone...

Страница 3: ...through the PC consult your TCS software manual PROGRAMMING THROUGH THE KEYPAD To access the programming screens press the program setup button Screens A thru F are monitoring screens and programming...

Страница 4: ...to two occupied periods SZ1062 only Schedule Announcement Screen Announces the next screen SZ1062 only Copy Schedule Screen Choose to use the same schedule that was used for the previous day If so the...

Страница 5: ...tput a stage of HEAT or a stage of COOL SZ1062 only Time Clock Output Screen Choose whether the auxiliary output will be OPEN or CLOSED during occupied periods This screen is not used if step 29 is se...

Страница 6: ...ime remaining elapses they may press the override button again Additionally an Override Hold feature is built into the thermostats When in unoccupied mode pressing the override once and then pressing...

Страница 7: ...em See setup instructions for dipswitch placement for this option The pipe temperature span is 0 to 150 F 17 8 to 65 6 C DIGITAL OUTPUTS The digital outputs on the SZ1061 and SZ1062 are used to contro...

Страница 8: ...NOTE The fan has a minimum on and off time of 30 seconds A relay for heating or cooling has a minimum on and off time of 2 minutes NOTE The SZ1061 does not show the day or time 2 Turn power on The th...

Страница 9: ...If any of the temperatures are still reading slightly high or low you can add in a temperature offset calibration using Ubiquity or TCS Insight In Ubiquity you can edit the calibration off set for eac...

Страница 10: ...80 minutes This value may be changed from 0 to 255 minutes in programming step 23 SETTING CLOCK SCHEDULE The ability to set the clock and schedule is allowed by factory default An access code may be r...

Отзывы: