-Setting up multiple Opticlimates on 1 water-cooler

When connecting more than one Opticlimate to 1 water cooler, it's important that pipe resistance 

(return and supply) for each Opticlimate is the same to prevent uneven water distribution between 

the Opticlimates.

The setup of the water cooler and pump etc. is the same as described in the chapter Setting up 1 

Opticlimate on 1 water-cooler. 

The layout of the piping from and to the Opticlimates must be well designed. It's best to consult us 

using a drawing or sketch of the situation on the Design sheet below.

-Setting up manual Fan/pump control

Tekening

The most simple and cheap way of fan and pump control is to power the pump always and 

connecting the fan of the water cooler to connection N and 7 inside the electric compartment of the 

Opticlimate.

The flow in this setup must be manualy adjusted with a valve in the piping between pump and water

cooler. The flow needs a periodic adjustment depending on outside temperatures.  ΔT between 

water-in and water-out of the Opticlimate needs to be 5K. More flow loweres  ΔT, less flow 

increases  ΔT.

© TCF 2019

Содержание 3500pro3

Страница 1: ...y the energy that must be circulated KW and the pressure depends on the pressure drop of the complete system Opticlimate s piping water cooler We always calculate the correct pump for your setup We suggest to place the pump indoor The piping We suggest to use PE piping with quick connectors Prevent knees or other fittings that reduce water flow We supply all the fittings for PE piping in the packa...

Страница 2: ...te on 1 water cooler The system is filled with water or glycol mix The water supply 8 must be located at the lowest point of the system Automatic bleeders 2 must be located at the highest point of the system A manometer 4 is positioned on the both the return and supply side of the pump The air separator 5 must be located at a location where the pressure in a running system is the lowest pump intak...

Страница 3: ...be well designed It s best to consult us using a drawing or sketch of the situation on the Design sheet below Setting up manual Fan pump control Tekening The most simple and cheap way of fan and pump control is to power the pump always and connecting the fan of the water cooler to connection N and 7 inside the electric compartment of the Opticlimate The flow in this setup must be manualy adjusted ...

Страница 4: ...mer On off model Opticlimate Inverter model Opticlimate When using an on off model Opticlimate find the cable that powers the compressor coming from relays KM1 Cable code U V or W When using an inverter model Opticlimate find the cable that powers the inverter PCB or compressor The current clamp can be opened to clamp around the cable Plug the other end into the controller The cable is labeled CO2...

Страница 5: ...plied communication cable to connect the controllers AUX connection on top with the fan aux box AUX IN connection on the left side The power outlet marked FAN on the fan aux box must be connected to the fan of the water cooler and the pump must be connected to the outlet marked RH The settings on the controller are pre set Do not change them without consultation Power both the controller and fan a...

Страница 6: ...rature supply to water cooler C03 Water in temperature return from water cooler Example C02 45 C C03 39 C ΔT 6 K Balancing with manual or auto by pass Adding glycol to the system In an environment where glycol antifreeze in case of a leak could come in contact with food chemicals or in a pharmaceutical or agriculture plant propylene glycol must be used We recommend to use a 20 glycol water mix ant...

Страница 7: ... the calculated amount of glycol then top up the system with water until the static pressure is 1 5bar When adding glycol to system that is already pressurised and full with water remove more water than the amount of glycol you want to add add the calculated amount of glycol and top up with water until the static pressure of the system is 1 5bar Note Pure water cools better than a glycol water mix...

Страница 8: ...__pro3 pro4 Distance between Opticlimates and water cooler_________________________________mtr Heat load Opticlimates KW _________________________________________________KW Max outside temperature ____________________________________________________ C Min outside temperature ____________________________________________________ C Sketch of the situation TCF 2019 ...