-Setting up multiple Opticlimates on 1 water-cooler
When connecting more than one Opticlimate to 1 water cooler, it's important that pipe resistance
(return and supply) for each Opticlimate is the same to prevent uneven water distribution between
the Opticlimates.
The setup of the water cooler and pump etc. is the same as described in the chapter Setting up 1
Opticlimate on 1 water-cooler.
The layout of the piping from and to the Opticlimates must be well designed. It's best to consult us
using a drawing or sketch of the situation on the Design sheet below.
-Setting up manual Fan/pump control
Tekening
The most simple and cheap way of fan and pump control is to power the pump always and
connecting the fan of the water cooler to connection N and 7 inside the electric compartment of the
Opticlimate.
The flow in this setup must be manualy adjusted with a valve in the piping between pump and water
cooler. The flow needs a periodic adjustment depending on outside temperatures. ΔT between
water-in and water-out of the Opticlimate needs to be 5K. More flow loweres ΔT, less flow
increases ΔT.