-deter-men ΔT and adjusting

The design  ΔT of the the system is 5K. This means that the temperature difference between the 

water-inlet and outlet of the Opticlimate must be maintained at 5K. To deter-men this value press 

the S-key short on the remote of the Opticlimate. In the display appears C-01 and a temperature. 

Using the up-and down keys you can scroll from C-01 up to C-06.

To determent  ΔT 

subtract the temperature value C02 from C03.

C02 – Water-out temperature  (supply to water cooler)

C03 -  Water-in temperature (return from water cooler)

Example: C02= 45°C

                C03= 39

°C -

                  ΔT=  6°K

-Balancing with manual or auto by-pass

-Adding glycol to the system

In an environment where glycol (antifreeze) in case of a leak could come in contact with food, 

chemicals or in a pharmaceutical or agriculture plant, propylene glycol must be used. We 

recommend to use a 20% glycol / water mix. (antifreeze protection -10°C) or more depending on 

outside conditions.

To determen how much glycol must be added, you need to know the total volume of water in the 

system. The specification sheets below help to determen how much volume your system contains.

© TCF 2019

Содержание 3500pro3

Страница 1: ...y the energy that must be circulated KW and the pressure depends on the pressure drop of the complete system Opticlimate s piping water cooler We always calculate the correct pump for your setup We suggest to place the pump indoor The piping We suggest to use PE piping with quick connectors Prevent knees or other fittings that reduce water flow We supply all the fittings for PE piping in the packa...

Страница 2: ...te on 1 water cooler The system is filled with water or glycol mix The water supply 8 must be located at the lowest point of the system Automatic bleeders 2 must be located at the highest point of the system A manometer 4 is positioned on the both the return and supply side of the pump The air separator 5 must be located at a location where the pressure in a running system is the lowest pump intak...

Страница 3: ...be well designed It s best to consult us using a drawing or sketch of the situation on the Design sheet below Setting up manual Fan pump control Tekening The most simple and cheap way of fan and pump control is to power the pump always and connecting the fan of the water cooler to connection N and 7 inside the electric compartment of the Opticlimate The flow in this setup must be manualy adjusted ...

Страница 4: ...mer On off model Opticlimate Inverter model Opticlimate When using an on off model Opticlimate find the cable that powers the compressor coming from relays KM1 Cable code U V or W When using an inverter model Opticlimate find the cable that powers the inverter PCB or compressor The current clamp can be opened to clamp around the cable Plug the other end into the controller The cable is labeled CO2...

Страница 5: ...plied communication cable to connect the controllers AUX connection on top with the fan aux box AUX IN connection on the left side The power outlet marked FAN on the fan aux box must be connected to the fan of the water cooler and the pump must be connected to the outlet marked RH The settings on the controller are pre set Do not change them without consultation Power both the controller and fan a...

Страница 6: ...rature supply to water cooler C03 Water in temperature return from water cooler Example C02 45 C C03 39 C ΔT 6 K Balancing with manual or auto by pass Adding glycol to the system In an environment where glycol antifreeze in case of a leak could come in contact with food chemicals or in a pharmaceutical or agriculture plant propylene glycol must be used We recommend to use a 20 glycol water mix ant...

Страница 7: ... the calculated amount of glycol then top up the system with water until the static pressure is 1 5bar When adding glycol to system that is already pressurised and full with water remove more water than the amount of glycol you want to add add the calculated amount of glycol and top up with water until the static pressure of the system is 1 5bar Note Pure water cools better than a glycol water mix...

Страница 8: ...__pro3 pro4 Distance between Opticlimates and water cooler_________________________________mtr Heat load Opticlimates KW _________________________________________________KW Max outside temperature ____________________________________________________ C Min outside temperature ____________________________________________________ C Sketch of the situation TCF 2019 ...