Energier pro User Manual
11
A group of dry contact input (Auxiliary In) was available on Energier pro bi-directional inverter, of which can be used to remotely
turn off the equipment.
Only Dry Contact.
Please find following chart the default setting:
2.18 Dry contact
Dry Contact Input
A group of dry contact output (Auxiliary Out) was available on Energier pro bi-directional inverter. The default setting of this dry contact
output was battery low voltage.It will activate once the voltage was detected dropping to preset level. This dry contact can be used for
load management or other function.
Through Vision Lite or Rapconfig, other functions can be configured for this contact.
Dry Contact Output
LVD setting
10.5 VDC
11.7 VDC
Default
11 VDC
12 VDC
Default
22 VDC
24 VDC
LVD setting
21 VDC
23.4 VDC
LVD setting
42 VDC
46.8 VDC
Default
44 VDC
48 VDC
The maximum contact load is:
230 VAC : 2 A
12 VDC / 24 VDC / 36 VDC : 2 A