background image

Energier pro User Manual

34

Please double check battery voltage match the model you are going to install, the wrong battery could destroy 
equipment and is out of warranty.

Please double confirm the polarity of battery input. Reverse polarity could cause permanent damage on equipment 
and it is out of warranty.

Choose the right cable size (refer to 5.3) and follow polarity guide marked on the panel.
Pull through the battery cables through the holes at front panel, clamping the cable terminal on cable.
Secure the battery cable on DC+ and DC- terminals respectively making sure it is tightly screwed.

If you are intending to use this charger, please follow the following steps:

Fail to connecting the minus terminal of starter battery to minus terminal of service battery might cause the 
slave charger fail to perform charging.

Use 2x2.5 mm² wire.
Connecting the POSITIVE (+) terminal of the starter battery to the terminal marked S+ output on central 
panel, see picture left.
The MINUS (-) terminal of starter battery should be connected to the minus terminal of your service battery.
Only 12 VDC / 24 VDC models (except CF5090M) has this slave charger.

AC input cable: choose the right cable size (refer to 5.3), pull through the AC input cable through Gland and connect it on AC input block. 
Connectors are marked as “L”-line, “N”-neutral and “PE”-earth. Making sure it is tightly screwed.
AC output cable: choose the right cable size (refer to 5.3), pull through the AC output cable through Gland and connect it on AC output
 block. Connectors are marked as “L”-line, “N”-neutral and “PE”-earth. Making sure it is tightly screwed.

Connecting battery cable of service battery.

Connecting Slave charger

Connecting the AC cable

Содержание Energier Pro Series

Страница 1: ...User Manual Energier Pro series Bi directional inverter TBB Power CO ltd www tbbpower com A3 1...

Страница 2: ...ergier pro User Manual WARNING FIRE HAZARD SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON COMBUS TIBLE SURFACE ONLY CAUTION THE DC AND AC BREAKER MUST HAVE BEEN TURNED OFF BEFORE SERVICING MADE IN CHI...

Страница 3: ...the inverter 2 Please connect positive terminal of battery to input of the inverter 3 Please connect negative terminal of battery to input of the inverter 4 Please use the shortest cable and ensure t...

Страница 4: ...el 6 2 9 Weak Grid 6 2 10 Solar mode 7 2 11 Gen mode 7 2 12 Power Save Mode PS mode 7 2 13 AGS Automatic Generator Start 8 2 15 Vision Lite control center 9 2 16 RCF remote module optional device 9 2...

Страница 5: ...Type 4 6 Equalization EQ 4 7 Power Save mode PS mode 4 8 GEN mode 4 9 AC input current setting 5 Pre Installation 5 1 Material list 5 3 Wiring recommendation 6 Installation and Connection 6 1 General...

Страница 6: ...sulphation Charging 42 8 Specification 44 9 Trouble Shooting 46 9 1 LED indicator on front panel and audible alarm 46 9 2 LED indicator on Remote 47 9 2 1 Operating status 48 9 2 3 Load percentage ba...

Страница 7: ...electric shock make sure all cables selected with right gauge and being connected well Smaller diameter and broken cable are not allowed to use 1 2 3 Please do not put any inflammable goods near to in...

Страница 8: ...endent power systems The product was delivered with following equipment Energier pro bi directional inverter user s manual TS battery temperature sensor VS battery voltage sensor optional RCF Remote m...

Страница 9: ...o a single enclosure Meantime multiple power management functions devices make it convenient to compose different advanced hybrid independent power systems Twin AC input devices TAI is available with...

Страница 10: ...ve High surge power Powerful Charger Fitted with multistage charging algorithm bulk absorption float recycle the built in charger of the Energier pro bi directional inverter is designed to charge batt...

Страница 11: ...tically adjust its output power making it suitable for the battery capacity selected The charging current default threshold rate is 15 of the battery capacity I 0 15C chosen 2 4 Slave Charger When vol...

Страница 12: ...e applied to Flooded and OPZS batteries As a protection the EQ mode will automatically disable if you select either LFP GEL OPzVor AGM as battery type 2 7 Manual Equalization Deep discharge of a lead...

Страница 13: ...nergier pro bi directional inverter offers the approach to fully adjust this entry level Please refer to chapter 7 11 for detail instruction You can also achieve this programming through optional Visi...

Страница 14: ...er has an internal or external AGS that can be used to start the Generator upon battery runs low To use this function the Generator needs to have automatic start function Upon battery runs to low volt...

Страница 15: ...ed input either grid or generator It can automatic allocate the power available with AC source either grid or genset using whatever extra for charging thus avoiding grid or generator to be overloaded...

Страница 16: ...ttery discharging to low protection alarm level through AGS Energier pro bi directional inverter will send signal to start Diesel Generator connected After detecting output of Diesel Generator was sta...

Страница 17: ...bi directional inverter The default setting of this dry contact output was battery low voltage It will activate once the voltage was detected dropping to preset level This dry contact can be used for...

Страница 18: ...ro bi directional inverter was fully programmable through PC of following parameters Battery charging parameters AC input range Switching parameters Battery configuration capacity type and low voltage...

Страница 19: ...can set its own preferred low voltage disconnect level Energier pro bi directional inverter will shut down upon battery voltage reach the preset level preventing battery to be over discharged or disc...

Страница 20: ...er Rated DC voltage 24V Rated output power 5000VA 4500W Rated charge current 90A With built in TAI field figure CF series name explanation 50 12 08 16 20 30 40 60 80 50 20 15 25 30 40 45 60 90 50A 20A...

Страница 21: ...al 15 1 CF0825L CF0815M CF1240L CF1220M CF1650L CF1625M 2 CF2060L CF2030M CF2015S CF3090L CF3045M CF3020S CF4030S 3 CF5090M CF6050S CF8060S CF5040S 3 Structure 3 1 Product drawing 3 1 1 Energier pro b...

Страница 22: ...Energier pro User Manual 16 3 1 2 RCF remote 3 1 3 Vision Lite 3 1 4 AGS 3 1 5 TAI...

Страница 23: ...Energier pro User Manual 17 2 CF2060L CF2030M CF2015S CF3090L CF3045M CF3020S CF4030S CF0825L CF0815M CF1240L CF1220M CF1650L CF1625M 3 2 1 Energier pro bi directional inverter 3 2 Product size...

Страница 24: ...Energier pro User Manual 18 3 CF5090M CF6050S CF8060S CF5040S 3 2 2 RCF remote 3 2 3 Vision Lite...

Страница 25: ...Energier pro User Manual 19 3 2 4 AGS 3 2 5 TAI...

Страница 26: ...Model CF 2000VA 4000VA Model 4 Pre installation Configuration Front Panel A B D C E F Gland for remote control cable Battery cable through hole Gland for AC output Battery cable through hole Gland for...

Страница 27: ...ion is being prepared for configuration through dipswitch In case you bought Vision Lite or Rapconfig please refer to Vision Lite or Rapconfig for detail introduction Loose screws and remove the top p...

Страница 28: ...AGS Interface AC Input terminals Auxiliary terminals Battery terminal Remote Interface B D C Battery terminal Slaver Charger terminal AC Output terminals F G E H I K J M N L Voltage Sensor terminals...

Страница 29: ...Input terminals DIP Switches Remote Interface BTS Interface B D C Battery terminal Battery terminal Slaver Charger terminal F G E I J L K N O AC Output terminals H M Auxiliary Out terminals Voltage Se...

Страница 30: ...s AC Output terminals RS485 Interface DIP Switches B D C Battery Terminal Battery terminal Chassis Ground F G E I J L K N O Generator Input terminals H P BTS Interface M AGSTerminal Voltage Sensor ter...

Страница 31: ...rger to get higher charging current However please make sure the current did not exceed 0 2C 20 of battery capacity 1 If you choose battery capacity at 200 AH you could get charging current of 15 x200...

Страница 32: ...le with only electrical parameter It may vary according to discharge current battery healthy etc 4 4 Low Voltage disconnect LVD Please refer to following chart for all setting of DIP Switch DIP Switch...

Страница 33: ...tery type at the DIP Switch 4 5 following please find the list of available battery type and charging voltage 4 5 Battery Type Through switch dip switch 6 with a cycle from OFF to ON to OFF you could...

Страница 34: ...er Save mode PS mode Through DIP Switch 1 and 8 you could configure the system to different modes for different appliance For explanation please refer to chapter 2 11 Through RCF supplied you can set...

Страница 35: ...g Forced air 5 1 Material list Please install the equipment in a location of Dry Clean Cool with good ventilation 5 2 Location Please find the following minimum wire size In case of DC cable longer th...

Страница 36: ...er performance of the equipment On the AC output side we recommend connecting the output from Energier pro bi directional inverter to a suitable Residual Current Circuit Breaker and Circuit Breaker Th...

Страница 37: ...example install on wall please choose a flat surface and with 4XM6 to fix the unit securely Steps for 800 4000 VA models Step 1 Fix the widget on the wall with 4 M6 screw Step 2 Pre installation pictu...

Страница 38: ...ansion screw Buckle the pothook of the unit into the expansion screw that was already fixed on the wall Step 3 Use the other 2 M6 expansion screws to fix the unit on the wall Please make sure Energier...

Страница 39: ...Energier pro User Manual 33 CF 2000 VA 4000 VA Model CF 5000 VA 8000 VA Model...

Страница 40: ...erminal of service battery might cause the slave charger fail to perform charging Use 2x2 5 mm wire Connecting the POSITIVE terminal of the starter battery to the terminal marked S output on central p...

Страница 41: ...f warranty The neutral output of Energier pro bi directional inverter is automatically connected to earth upon no external sources is available Once external AC sources present the ground relay will o...

Страница 42: ...chment Please notice the cable supplied is around 300cm Do not pull cable too hard avoid loose contact loose Pull through the VS cable through gland and connect it on port marked Voltage Sensor Please...

Страница 43: ...able please refer to following figure Connect the Vision Lite to the RS485 interface of Energier pro bi directional inverter with the cable please refer to following figure 6 6 Install the RCF remote...

Страница 44: ...ng the output on terminal marked OUT Please double check the polarity of the input and output Wrong connection will damage the equipment and it is out of warranty TAI need to be connected with Energie...

Страница 45: ...not present Energier pro bi directional inverter will go to inverter mode automatically In case the user does not want to use the inverter mode but wants the batteries to be fully charged the CHG ONLY...

Страница 46: ...mode feeding the power to load and meantime battery charger will start work The bypass LED and charger LED on front panel will illuminate The AC in LED and Charger LED on remotewill illuminate While c...

Страница 47: ...5 on remote will illuminate The charging LED on front panel will flash The Bulk Battery SOC 25 LED and ABS Battery SOC 50 LED on remote will illuminate Along with more energy being charged into batter...

Страница 48: ...on sealed batteries Energier pro bi directional inverter includes a manual equalization program that can be used if recommended by battery manufacturer Through the dip switch at central panel you can...

Страница 49: ...to OFF after each time s equalization Battery manufactures recommendations on equalization vary Always follow the battery manufacturer s instructions so batteries are properly equalized As a guide a h...

Страница 50: ...150 200 CF2015S CF3020S CF4030S CF8060S TAI 20 s 800 1100 1000 1200 1300 1200 1600 1600 1450 2000 2500 2200 3000 3500 3200 4000 4500 4000 5000 5000 4500 6000 7000 6000 8000 Bypass range 89 92 95 3 1...

Страница 51: ...e 12VDC and 24Vdc model only Slave Charger 4mV cell Temperature compensation Other Data Transfer time 2 s 15ms Battery low Dry contact Battery connector M6 x 2 M8 x 2 440 232 5 95 10 5 11 65 11 9 18 1...

Страница 52: ...lash flash Float Stop charging Power Save mode Battery low voltage flash Battery overvoltage flash Inverter overload flash Inverter overtemp Alarm Mode Protection mode beep 0 5s every 1s beep continuo...

Страница 53: ...ge Function Constant voltage Constant current Float EQ Inverter ON Power Save mode Battery overvoltage Inverter overload Inverter overtemp Bypass overload Over charging AEA limited flash Battery low v...

Страница 54: ...se polarity Solution Replace PCB 9 3 1 No output first power on Phenomenon 4 No output fault and overload lights illuminate Reason Overload shutdown Solution Reducing load and switch on again Phenomen...

Страница 55: ...he load was fluctuating Solution Change work mode to normal mode 9 3 5 Normal mode or Charger Only mode not working Reason 1 The work mode setting on Energier pro bi directional inverter and on RCF wa...

Страница 56: ...POWER CO LTD Web www tbbpower com Tel 86 592 5212299 Fax 86 592 5796070 Email service tbbpower com TBB POWER GmbH Web www tbbpower de Tel 49 0 211 6413 7949 Fax 49 0 211 6415 0003 Email info tbbpower...

Отзывы: