MPPT charge controller User Manual
1
Table 3-3 Breaker Requirement
NO.
Parts
Description
Requirement
1
Battery breaker
SP100-40
(1) The voltage requirement is greater than 63V.
(2) The current requirement is greater than 63A.
SP100-20
(1) The voltage requirement is greater than 63V.
(2) The current requirement is greater than 32A.
SP50-40
(1) The voltage requirement is greater than 63V.
(2) The current requirement is greater than 63A.
SP50-20
(1) The voltage requirement is greater than 63V.
(2) The current requirement is greater than 32A.
2
PV array breaker
SP100-40
(1) The voltage requirement is greater than100V.
(2) The current requirement is greater than 40A.
SP100-20
(1) The voltage requirement is greater than 100V.
(2) The current requirement is greater than 32A.
SP50-40
(1) The voltage requirement is greater than 50V.
(2) The current requirement is greater than 40A.
SP50-20
(1) The voltage requirement is greater than 50V.
(2) The current requirement is greater than 32A.
3.4.3 Cable Preparation
Cable with minimum 90
℃
(194F) insulation rating was recommended to be used for SP
installation.
Minimum wire size requirements are shown in the Table 3-4
Table 3-4 Recommended DC wiring
Model
Recommended DC wiring
2 meters
3 meters
5 meters
7 meters
10A
12AWG
4mm²
12AWG
4mm²
10AWG
6mm²
8AWG
10mm²
20A
10AWG
6mm²
10AWG
6mm²
8AWG
10mm²
6AWG
16mm²
30A
10AWG
6mm²
8AWG
10mm²
6AWG
16mm²
6AWG
16mm²
40A
8AWG
10mm²
6AWG
16mm²
6AWG
16mm²